Printed in U.S.A.

Page 16

MODEL 3210 ECONOMINDER

Commercial Demand Regeneration Control

Timer Settings

Typical Programming Procedure

Calculate the gallon capacity of the system, subtract the
necessary reserve requirement and set the gallons
required by lifting the gallon dial and rotating it so that the
number of gallons required is aligned with the white dot
on program wheel gear. Release and check for firm
engagement with gear. Note, drawing shows 8,750 gallon
setting. The capacity (gallons) arrow denotes remaining
gallons exclusive of fixed reserve.

Note:

To set meter capacity at initial start-up, either:

1. Rotate manual regeneration knob one full revolution.

or

2. Rotate program wheel manually clockwise or counter

clockwise and align white dot with capacity arrow.

This procedure must be followed any time the program
wheel setting is changed.

How To Set The Time Of Day:

Press and hold the red button in to disengage the 24 hour
gear.
Turn the 24 hour gear until the actual time of day is at the
time of day pointer.

Release the red button to again engage the 24 hour gear.

How To Manually Regenerate Your Water Conditioner
At Any Time:

Turn the manual regeneration knob clockwise one “click.”

This slight movement of the manual regeneration knob
engages the program wheel and starts the regeneration
program.

The black center knob will make one revolution in the
following approximately three hours and stop in the
position shown in the drawing.

Even though it takes three hours for this center knob to
complete one revolution, the regeneration cycle of your
unit might be set for only one half of this time.

In any event, conditioned water may be drawn after rinse
water stops flowing from the water conditioner drain line.

Immediate Regeneration Timers:

These timers do not have a 24 hour gear. Setting the
gallons on the program wheel and manual regeneration
procedure are the same as previous instructions.

* 24 HOUR

GEAR

SERVICE
POSITION
INDICATOR

RED TIME
SET BUTTON

WHITE DOT

GALLONS LABEL

PROGRAM

MANUAL
REGENERATION
KNOB

WHEEL

* Immediate regeneration timers do not have 24 hour gear. No time of day can be set.