Watts LFU5B-Z3 User Manual

Series lfu5b, Lead free, Water pressure reducing valves

Advertising
background image

For Residential and Commercial Applications

ES-LFU5B

Series LFU5B

Water Pressure Reducing Valves**

Sizes:

1

2

" – 2" (15 – 50mm)

Series LFU5B Water Pressure Reducing Valves are designed to reduce

incoming water pressure to a sensible level to protect plumbing system

components and reduce water consumption. The LFU5B features Lead Free*

construction to comply with Lead Free* installation requirements. This series

is suitable for water supply pressures up to 300psi (20.7 bar) and may be

adjusted from 25 – 75psi (172 – 517 kPa). The standard setting is 50psi

(345 kPa). All parts are quickly and easily serviceable without removing

the valve from the line. The LFU5B’s standard bypass feature permits the

flow of water back through the valve into the main when pressures, due to

thermal expansion on the outlet side of the valve, exceed the pressure in the

main supply.

Features

•   Standard construction includes Z3 sealed spring cage and stainless steel 

corrosion resistant adjusting cage screws for accessible outdoor

or

pit installations

•  Integral stainless steel strainer

•  Replaceable seat module

•  Lead Free* cast copper silicon alloy body construction

•  Serviceable in line

•  Bypass feature controls thermal expansion pressure (LFU5B-Z3)***

•  High temperature resistant reinforced diaphragm for hot water

Models

LFU5B-Z3 

 NPT threaded female union inlet x NPT female outlet w/built in 

thermal expansion bypass

LFU5B-S-Z3 

 Solder union inlet x NPT female outlet w/built in thermal 

expansion bypass

LF5M3-Z6 

 Water meter threaded connections and 7

1

2

" (190mm) lay

length for new or existing meter box installations. For

5

8

"

(16mm), 

5

8

" x

3

4

" (16 x 20mm) or 

3

4

" (20mm) meter

setters or resetters

LFU5B-QC-Z3   Quick-Connect Single-Union – Inlet end

Specifications

Standard Specifications: A Water Pressure Reducing Valve with integral

strainer shall be installed in the water service pipe near its entrance to the

building where supply main pressure exceeds 60psi (413 kPa) to reduce 

it to 50psi (345 kPa) or lower. The water pressure reducing valve shall be

constructed using Lead Free* materials. Lead Free* regulators shall comply

with state codes and standards, where applicable, requiring reduced lead

content. The valve shall feature a Lead Free* cast copper silicon alloy body

suitable for water supply pressures up to 300psi (20.7 bar). Provision shall

be made to permit the bypass flow of water back through the valve into the

main when pressures, due to thermal expansion on the outlet side of the

valve, exceed the pressure in the main supply. Water Pressure Reducing

Valve with built-in bypass check valves will be acceptable. Approved valve 

shall be listed to ASSE 1003 and IAPMO and certified to CSA B356. Valve 

shall be a Watts Series LFU5B-Z3.

LFU5B-Z3

Sensitive spring and large diaphragm

area provide for accurate pressure

control and wide range of adjustment.

High temperature resisting dia-

phragm for hot or cold water.

Lead Free* copper

silicon alloy body

construction

Stainless steel seat

Large integral

stainless steel

strainer screen

easily removed

for cleaning.

Disc holder removable

for replacement of disc

without dismantling

the valve - no special

tools required.

Suffix B Bypass feature

Spring (not shown)

“LP” Model only

Expanded

Pressure

Initial

Pressure

Reduced

Pressure

Inlet Seat and Disc

Suffix B

Thermal Expansion Bypass Check Valve Feature

LEAD FREE

*

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

** A water saving test program concluded that reducing the supply

pressure from 80-50psi (551-345 kPa) resulted in a water savings of
30%.

*** The bypass feature will not prevent the pressure relief valve from

opening on the hot water supply system with pressure above 150psi
(10.3 bar).

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Advertising