background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.watts.com

M

ustang

s

eries

Specifications

M6115-7 (Globe)

M61115-7 (Angle)

The Pressure Reducing and Downstream Surge Control Valve shall be a pilot operated diaphragm valve

designed to automatically reduce a fluctuating higher upstream pressure to a constant lower downstream

pressure regardless of varying flow rate, and quickly modulate toward a closed position when a sudden high

pressure downstream condition occurs.

The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.

Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms

a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm

shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall

be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there

shall be no pistons operating the main valve or any pilot controls.

The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall

be Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover,

shall be lined and coated with an NSF 61 Certified Epoxy Coating applied by the electrostatic heat fusion

process. All main valve trim and throttling components (cover bearing, valve seat and disc guide) shall

be Stainless Steel. The valve body and cover must be machined with a 360-degree locating lip to assure

proper alignment.

The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular cross-

section that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies

utilizing bolts or cap screws for component retention will not be permitted.

The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm

assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically

located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided

valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body

remains in line.

Pilot control systems for 3” valves shall contain a Flow Clean Strainer, Fixed Orifice Closing Speed,

Adjustable Opening Speed Control, Downstream Surge Control Pilot and Pressure Reducing Pilot. Pilot

control systems for valves 4” and larger shall contain an external Y-Strainer, Fixed Orifice Closing Speed,

Downstream Surge Control Pilot, Pressure Reducing Pilot and Isolation Ball Valves on all body connections.

All pilot control systems shall utilize copper tubing and brass fittings regardless of valve size. The adjustment

range of the surge control pilot shall be 20-200 psi and the pressure reducing pilot shall be 30-300 psi.

The valve shall be Watts ACV Model M6115-7 (Globe) or M61115-7 (Angle) pattern Combination Pressure

Reducing and Surge Control Valve.

Other Watts ACV Pressure Reducing Control Valves

M6115 / M61115

Pressure Reducing Valve

M6115-3 / M61115-3 Pressure Reducing Valve with Hydraulic Check Feature

M6115-74 / M61115-74 Pressure Reducing Valve with Low Flow By-Pass

910 Ops & Inst