M6115-3 (Globe)

M61115-3 (Angle)

Proper Automatic Control Valve start-up requires bringing the valve into service in a controlled manner. All

adjustments to control pilots and speed controls should be made slowly, allowing the valve to respond and

the system to stabilize.

NOTE: Control Valves should be set‑up in a dynamic (flowing) condition for

proper start‑up. Provisions for flow must be made to insure proper settings.

Close upstream and downstream valves to isolate the valve from line pressure. Release spring ten-

1.

sion on Pressure Reducing Control by turning adjustment screw out (counterclockwise), decreas-

ing setpoint. Open all Isolation Ball Valves, if so equipped. If valve is fitted with adjustable speed

controls, turn needle(s) in (clockwise) until seated, and return out (counterclockwise) 1-1/2 to 2-1/2

turns. These are approximate settings, and should be fine tuned to suit system requirements after

pressure adjustments have been made.

Slowly open upstream isolation valve to allow controlled filling of the valve. Vent entrapped air by

2.

carefully loosening control tubing or pipe plug at the highest point possible. If valve is equipped

with a Position Indicator, open Air Bleed Petcock to vent air. Water will be milky in appearance and

will begin to clear as air is vented. Carefully loosen enough cover screws on control pilot(s) to vent

entrapped air. Re-tighten when water vents clearly.

Setting Reducing Control:

3.

Slowly open downstream isolation valve. Gradually turn adjustment

screw on the Pressure Reducing Control in (clockwise) to raise downstream pressure. Allow valve

and system to stabilize. Observe inlet and outlet pressure gauges. Continue to adjust as needed,

pausing approximately every 1-1/2 turns, allowing valve and system to stabilize. Turning adjustment

screw clockwise raises outlet pressure. Turning adjustment screw counterclockwise lowers outlet

pressure. When desired downstream pressure is reached, tighten locknut on adjustment screw.

Fine tune Speed Controls to suit system requirements. Adjust Closing Speed Control (if equipped)

4.

clockwise for slower closure, and counterclockwise for faster closure. Adjust Opening Speed Con-

trol (if equipped) clockwise for slower opening, and counterclockwise for faster opening.

Installations

Start-Up

Prior to installation, flush line to remove debris.

Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line.

Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than

described.

Install inlet and outlet isolation valves.

NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

Provide adequate clearance for valve servicing and maintenance.

Install pressure gauges to monitor valve inlet and outlet pressure.

If installation is subjected to very low flow or potentially static conditions, it is recommended a pressure

relief valve (1/2” minimum) be installed downstream of the Pressure Reducing Valve for additional system

protection.