Watts LFL1170 User Manual

Lead free, Hot water temperature control valves, Sizes

Advertising
background image

For Residential, Commercial and Institutional Applications

ES-LF1170_LFL1170

Job Name –––––––––––––––––––––––––––––––––––––––––––– Contractor

––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––– Approval

––––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative

–––––––––––––––––––––––––––––––––––––––––

Hot Water Temperature Control

Valves

Sizes:

1

2

" – 1"

Series LF1170, LFL1170 Hot Water Temperature Control Valves are

specifically designed for mixing hot and cold water on hot water supply

systems. They can be used for a variety of applications to reduce the

temperature of the hot water from the system and are ideal for radi-

ant heat applications. This series features a “double throttling” design

which combines the control of the hot and cold water to provide a

sensitive response to changes in water temperature passing through

the mixing chamber.
The LF1170-M2 can be set to any temperature between 90°F and

160°F (60°F and 120°F for model LFL1170-M2) with flow rates as

low as 0.5 gpm and as high as 23 gpm (refer to capacity chart on the

back). The superior flow characteristics of this valve provide accurate

temperature control to the requirements of ASSE 1017** across the

rated flow range. The LF1170 and LFL1170 feature Lead Free* con-

struction to comply with Lead Free* installation requirements.
These valves also provide additional safety as they restrict mixed

water out to a drip upon loss of cold water supply to the valve.
As an added feature, the LF1170-M2 and LFL1170-M2 incorporate

integral check valves and filter washers in both the hot and cold water

inlets to protect against cross flow. Available with threaded (-UT),

solder (-US), PEx (-PEx), Quick-Connect (-QC) or CPVC (-CPVC)

connections.

Features

• Lead Free* cast copper silicon alloy body construction
• Solid wax hydraulic principle thermostat assures dependable

mixing of hot and cold water

• Thermostat controls both hot and cold water
• Models available with solder, thread, PEx, Quick-Connect

or CPVC end connections

• Integral filter washers and check valves
• Adjustment cap with locking feature
• ASSE 1017 listed**and IAPMO UPC

LF1170-US-M2

Minimum flow requirements to maintain set temperature

for Series LF1170-M2

ValVe Size

gpm

1

2

" – 1"

.5

LF1170-QC-M2

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

**ASSE 1017 listing is for valves used in hot water source applications.

LEAD FREE

*

Series LF1170 and

LFL1170

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

FAILURE TO COMPLY WITH PROPER INSTALLATION AND

MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO

THE VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for

tempering water temperature at fixtures. Severe bodily injury

(i.e., scalding or chilling) and/or death may result depending

upon system water pressure changes and/or supply water

temperature changes. ASSE standard 1016, 1069 or 1070

listed devices should be used at fixtures to prevent possible

injury.
These Hot Water Tempering Valves are designed to be installed at

or near the boiler or water heater. They are not designed to com-

pensate for system pressure fluctuations and should not be used

where ASSE standard 1016, 1069 or 1070 devices are required.

These valves should never be used to provide “anti-scald” or

“anti-chill” service.
The components of the system must be of materials with a con-

struction capable of withstanding the high limit output tempera-

tures of the water heating source.

WARNING

!

WARNING

!

Need for Periodic Inspection and Yearly Maintenance:

Periodic inspection and yearly maintenance by a licensed

contractor is required. Corrosive water conditions, inlet

temperatures over 200°F (93°C), and/or unauthorized adjust-

ments or repair could render the valve ineffective for service

intended. Regular checking and cleaning of the valve’s inter-

nal components and check stops helps assure maximum

life and proper product function. Frequency of cleaning and

inspection depends upon local water conditions.