Stainless series, Pump control valve with rate-of-flow feature – Watts S1113-41 User Manual

Page 2

Advertising
background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

01/05

R

Stainless Series

PUMP CONTROL VALVE with
RATE-OF-FLOW FEATURE

S113-41 or S6113-41 (Globe)

S1113-41 or S61113-41 (Angle)

Installation Guidelines

• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the valve with the sensing

connections offset from top of pipeline to avoid air accumulation. The Orifice Plate Assembly should not
be installed next to a butterfly valve.

• Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field

installed) in accordance with factory piping schematic.

• Connect Solenoid and Limit Switch to appropriate pump control panel locations and power source in

compliance with local electrical codes.

Other Watts ACV Pump Control Valves

S113-21 / S6113-21

Pump Control Valve

S113-19 / S6113-19

Pump Control Valve with Backpressure Feature

S113-29 / S6113-29

Pump Control Valve with Pressure Reducing Feature

S513-5 / S6513-5

Pump Control Valve

S513-AK / S6513-AK Pump Control Valve with High Capacity Pilot System
S513-6 / S6513-6

Deep Well Pump Control Valve

S513-14 / S6513-14

Deep Well Pump Control Valve with Pressure Relief Feature

Advertising
This manual is related to the following products: