Setup Using PC Setup Software
The transmitter can also be calibrated using a HART Modem and a PC. Kenco can supply software, at no charge, to
perform calibration by this method. Contact Kenco for more information.

The following parameters can be viewed / changed using this software:

Basic --

Manufacturing Information

Advanced --

Gauge Length, Gradient, Head Adder, Enable Display, Enable Loop 2, and Set Alarm Output

Calibration -- Level 1 Span and Offset (Zero), Level 2 Span and Offset, Temperature Span and Offset.

Output --

Level 1 Units of Measure, Level 2 Units of Measure, Temperature Units of Measure, Output Units of
Measure, Output Designations, and View Output Data.

1 Device setup >>
2 *PV
3 *AO
4 *PV URV
5 *PV LRV

1 Process Vars >>

2 Diag/Service >>

3 Basic setup >>

4 Detailed setup >>

5 Review >>

1 View Measurements
2 View PV-Analog 1
3 View SV-Analog 2
4 View TV
5 View 4V

1 Level Range Cal >>

2 Self Test

1 Calibrate Level 1
2 Calibrate Level 2
3 Exit

1 #Tag
2 Eng unit
3 Range Values
4 Device Information >>

5 #Damp

1 Model Data
2 Comm Parameters
3 #Sensr s/n
4 Final asmbly num
5 Descriptor
6 Message
7 # Date

1 Instrument Config >>

2 Float Offset
3 #PV is
4 Change PV
5 #SV is
6 Change SV
7 #TV is
8 Change TV
9 #4V is

Change 4V

1 System Config
2 Sys Config 2
3 Gradient
4 #Length
5 #Head Adder

“Review all Parameters”

LEGEND

* Dynamic variable
at right

# Value displayed at
right

>> Submenu
Selection

Bold: Config/View in
submenu