8.3 Protection

8.3.1 Three Minutes Delay at restart for compressor.

8.3.2 Temperature protection of compressor top.

8.3.3 If the temperature of compressor top is too high(higher than 115℃ and the Over-load Protector is cut, the units

stop. When the Over-load Protector restore and close(lower than 100℃), the compressor will restart( in this case

the compressor is restricted by Three Minutes Delay protection.

8.3.4 Temperature protection of compressor exhaust.

If the exhaust temp. of compressor is higher than 115℃ and lasts for 5 seconds, the compressor stops and does not

resume until the exhaust temp. is lower than 90℃.

8.3.5 Inverter module Protection, Inverter module Protection itself has a protection function against current, voltage

and temperature. If these protections happened, the corresponding code will display on indoor unit LED.

8.3.6 Sensor protection at open circuit and breaking disconnection

8.3.7 Fan Speed is out of control. When Indoor Fan Speed is too low (lower than 300RPM for 60 seconds), the unit

stops and LED displays failure information and can’t return

to normal operation automatically.

8.3.8 Cross Zero signal error warning. If there are 20 alternations of Cross Zero signals are incorrect, the unit stops

and LED displays failure information. After resuming, the motor rotates again. The spacing of Cross Zero signal

is 6-13ms.

8.3.9 Indoor fan delayed open function

8.3.10 For all modes, when the units are turned on, the indoor fan can operate 10 seconds after the action of louver.

8.3.11 Compressor preheating function.

1) Preheating

permitting

condition:

If T4(outdoor ambient temperature)<3℃ and the machine connects to power supply newly or if T4<3℃

and compressor has stopped for over 3 hours, the compressor heating cable will work.

2) Preheating

mode:

A weak current flows through the coil of compressor from the wiring terminal of compressor, then the

compressor is heated without operation.

3) Preheating

release

condition:

If T4>5℃ or user turns on the machine and compressor runs, preheating function will stop.

8.4 Fan-Only Mode

8.4.1 Temperature setting function is disabled, and no setting temperature display.

8.4.2 In this mode, the action of louver is the same as in cooling mode.

8.4.3 The action of auto fan in fan-only mode is the same as auto fan in cooling mode with 24℃ setting temperature.

T1

24

medium

3.5

3.0

1.5

1.0

high

low