Installation, continued – Powers 450 Infrared ESP HydroPanel II Infrared Sensor System User Manual

Page 2

Advertising
background image

WARNING: Before installing solenoid, flush the pipes to

ensure supply water is free of grit and sand.
NOTE:

A service stop can be installed directly upstream of the

solenoid to facilitate maintenance and repair.
The brass solenoid has 1/2" NPT end connections.
Connect the supply line to the solenoid, using only thread

sealant on male threads.

Do not use Teflon tape; it will clog

the solenoid valve. Connect the inlet piping so water flows in

the direction of the arrow on the solenoid. To mount the upper

bracket of the piping assembly, drill the holes at the same

height as the top of the showerhead (B and B’)

.

Install Modular Junction Box
The Modular Junction Box (MJB) with standard cables, can

be positioned up to 2 feet from the infrared sensor and up to

2 feet from the solenoid valve. [Optional cable extensions can

extend these distances to 1000 feet from the infrared sensor,

and 300 feet from the solenoid valve.] Remove the cover. Use

the box as a template to mark positions on the wall for two

mounting screws. Drill holes and attach the box.
Connect one of the power supply wires (supplied with ESP kit)

to the terminals. Tighten the screws for a secure connection.

Replace the cover.

Install the Transformer
The plug-in and box mount transformers can be positioned

in a chaseway, closet or ceiling. Each can power up to eight

solenoids. For shower system maintenance, a remote shut-off

switch can be installed.
WARNING: Do not supply power to or plug in the transformer

until all wiring is complete.

• Box Mount Transformer
The box mount transformer will mount on a 110V AC sup-

ply electrical junction box. The “J” box should be inside the

chase wall or above the ceiling. Connect the power supply

wires from the MJB to the secondary side of the transformer

(Figure 5). Tighten the screws.

Position the ESP Hydropanel II Unit
Determine the horizontal position of the unit according to

shower room layout, and mark the centerline (Figure 3). For

multiple shower applications, the recommended minimum dis-

tance between the centerline of two units is 36 inches.

Determine the floor-to-showerhead height for the unit.

Recommended shower head heights are listed below:

Men

77" [1955.8mm] - Youth 66" [1676.4mm]

Women 70" [1778mm] - Youth 60" [1524mm]

Determine where the inlet piping will connect to the solenoid.

For the non-metallic solenoid, this connection is typically

1-1/2" below showerhead height,

and 2-1/4" left of centerline. For a

brass solenoid, it is 2-1/2" below

showerhead height, and 2-1/4" left

of centerline (refer to Figure 3).

Install the Solenoid and

Piping Assembly
The piping and Hydropanel II

shrouding come pre-assembled

(Figure 4). To detach, remove the

screws at the showerhead (A) and

bottom bracket (C and C’). Slide the

piping out of shrouding; the show-

erhead remains part of the shroud.

IS-P-450S Page 2

A

B

B'

C

D

C'

End Cap

7-1/2

[190.5]

7/16

[11.11]

7-3/32

[180.18]

11/16

[17.46]

2-1/2
[63.5]

4-3/4

[120.65]

FLOOR LINE

C for Solenoid

L

2-1/4

[57.15]

2.5 [63.5] Brass
1.5 [38.1] Non-Metallic

C for Hydropanel unit

L

30

[762.0]

6

[154.4]

SOLENOID INLET
1/2" NPT Brass
3/4" NPT Non Metallic

77

[1955.8]

19-1/4

[488.95]

2

[50.8]

2-1/2
[63.5]

1-1/4
[31.8]

attach wires

Installation, Continued

n

For Suggested Showerhead Heights see Installation:

Positioning the ESP Hydropanel II unit

Figure 3. Front and side views -

Dimensions of the ESP Hydropanel II Infrared Shower

Figure 4.

Figure 5.

Advertising