INSTALLATION

Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier
immediately.
If undamaged, open the package and inspect the device for obvious
damage. Return damaged products.
Requirements

• Pipe wrenches
• Flange gaskets, bolts/nuts
• Installer must be a qualified, experienced technician

CAUTION!

• Install the valve with the flow in the direction of the flow arrow. (“A”

port is the inlet and “AB” is the outlet.)

• Do not exceed the ratings of the device.
• Avoid locations where excessive moisture, corrosive fumes, or

vibration are present.

Mounting/Orientation

1. The valve should be mounted in a location that is within the

ambient limits of the actuator. When selecting a location, allow
sufficient room for valve linkage, actuator, and other accessories
and for service of the product.

2. The preferred mounting position for the valve is with the valve

stem vertical above the valve body. Avoid mounting the valve so
that the valve stem is below horizontal.

3. On steam applications where the ambient temperature

approaches the limit of the actuator, the valve stem should
bemounted 45° from vertical.

Flanged Connection
The 597SI series flanged valve bodies conform to American Standard 125
Lb. Cast Iron Pipe Flanges. The companion flanges (not provided) should
be the same specification as the valve. The 125 lb. flanges have plain flat
faces and should not be bolted to a raised faced flange.

1.

All parts should be clean to assure the best results.

2.

The pipe with the companion flanges installed should be
properly supported and aligned. Be sure the companion flange is
flush with the face of the valve body flange and lined up
squarely.

3.

Use a gasket material (not provided) that is recommended for
the medium being handled.
CAUTION! Do not apply pipe dope to the valve flange, gasket,
or companion flange.

4.

See Figure-5 for flange and flange bolt details.
Figure-6 shows the proper way a flanged valve should be
mounted.

MAINTENANCE

Regular maintenance of the total system is recommended to assure sustained performance. See Table-6 for maintenance kit part numbers.

Table - 6 Maintenance Kits for 597SI Valves

Valve Description

Replacement

Replacement

Valve Repair Kit*

Packing Assembly

Gaskets

2.5 Normally Closed

597 Pack

597250G

597 SIGOBCTK

3 Normally Closed

597300G

597 SIHOBCTK

4 Normally Closed

597400G

597 SIJOBCTK

5 Normally Closed

597500G

597 SIKOBCTK

6 Normally Closed

597600G

597 SILOBCTK

2.5

Normally Open

597250G

597 SIGOBXTK

3 Normally Open

597300G

597 SIHOBXTK

4 Normally Open

597400G

597 SIJOBXTK

5 Normally

Open

597500G

597 SIKOBXTK

6 Normally

Open

597600G

597 SILOBXTK

* Kit includes replacement packing and stem & plug assembly.

Water System Maintenance
All systems are susceptible to valve and system problems caused by improper
water treatment and system storage procedures. These guidelines are
provided to help avoid valve and water system problems resulting from
improperly treated water or storage procedures and to obtain maximum life
from the valves.

Durability of valve stems and packings is dependent on maintaining non-
damaging water conditions. Inadequate water treatment or filtration can
result in corrosion, scale, and abrasive particle formation. Scale and

particulates can result in stem and packing scratches and can adversely affect
packing life and other parts of the hydronic system.
To maintain non-damaging conditions, follow these guidelines:

• Clean the system prior to start up.
• Use filtration equipment where needed.
• Properly store off-line systems and monitor water treatment results.
• Follow the advice of a water treatment professional.

Valve
Body

Gasket:
Supplied
by Others

Companion
Flange

Figure 6 - Installation of

Flanged End Valves