Specifications

n

Accritem Controller

Model 3

Technical Instructions

IS-P-TC744-1

Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Direct or Reverse Acting

Adjustment Dial Range—Standard 50 to 350°F (10 to 177°C)
Maximum Supply Pressure (air or water)

at Room Temperature

. . . . . . . . . . . . . . . . . . . . . . . . . .

35 psi (241.3 kPa)

Air Consumption (max.)

. . . . . . . . . . . . . . . . . . . . . . . . .

218 cm 3/s (800 SCIM)

Maximum Operating Pressure

. . . . . . . . . . . . . . . . . . . . . .

1724 kPa (250 psi)

Maximum Operating Temperature

. . . . . . . . . . . . . . . . . . . . . . . .

400°F(204°C)

Temperature Response

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

0.5°F(0.3°C )

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/2" NPT

Air or Water Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/8" NPT

Drain Connection (water only)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1/4" NPT

Shipping Weight

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 lbs. (1.8 kg)

Sensitivity (adjustable)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 to 27.9 kPa/C

(1/4 to 2-1/4 psi/F)

Maximum Pressure on Wells

Stainless Steel no. 744-082

. . . . . . . . . . . . . . . . . .

1125 psi (7756 kPa)

Copper no. 744-111

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

525 psi (3619 kPa)

Well Dimensions

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

See page 6

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-

mation can result in death, serious personal injury,

property damage, or damage to the equipment.
Keep this Manual for future reference.

AiR OpERAtEd:

Rigid Stainless Bulb

Direct Action

744-1270

Reverse Action 744-1271

Rigid Copper Bulb

Direct Action

744-1213

Reverse Action 744-1214

WAtER OpERAtEd:

Rigid Stainless Bulb

Direct Action

744-1217

Reverse Action 744-1218

You are required to consult the local building and plumbing

codes prior to installation. If the information in this manual is

not consistent with local building or plumbing codes, the local

codes should be followed. Inquire with governing authorities for

additional local requirements.

WARNING

!

WARNING

!

Flush all pipes thoroughly before installation. Installation and

field adjustment are the responsibility of the installer.

WARNING

!

Need for periodic inspection and Yearly Maintenance:

Periodic inspection and yearly maintenance by a licensed con-

tractor is required. Corrosive water conditions and/or unauthor-

ized adjustments or repair could render the valve ineffective for

service intended. Regular checking and cleaning of the valve’s

internal components and check stops helps assure maximum

life and proper product function. Frequency of cleaning and

inspection depends upon local water conditions.

FAiLURE tO COMpLY WitH pROpER iNStALLAtiON ANd

MAiNtENANCE iNStRUCtiONS COULd CONtRiBUtE tO tHE

VALVE FAiLURE.
this Hot Water Master tempering Valves cannot be used for

tempering water temperature at fixtures. Severe bodily injury

(i.e., scalding or chilling) and/or death may result depending

upon system water pressure changes and/or supply water

temperature changes. ASSE standard 1016, 1069 or 1070 listed

devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be

installed at or near the boiler or water heater. They are not

designed to compensate for system pressure fluctuations and

should not be used where ASSE standard 1016, 1069 or 1070

devices are required. These valves should never be used to

provide “anti-scald” or “anti-chill” service.
The components of the system must be of materials with a

construction capable of withstanding the high limit output tem-

peratures of the water heating source.