Powers ETV400 Emergency Tempering Valves with Internal Cold Water Bypass User Manual

Technical instructions

Advertising
background image

HydroGuard

®

XP Emergency Tempering valves thermostatically blend hot and cold

water to deliver tepid water to emergency fixtures, quickly compensating for tem-

perature variations due to the changes in inlet temperature or pressure. Powers'

exclusive internal bypass ensures cold water flow in the event of loss of hot water.

US Patent Pending

Description

n

Connections (NPT)

ETV200

.............................................. 3/4" inlets, 1" outlet

ETV400

.............................................. 1-1/4" inlets, 1-1/2" outlet

ETV500

.............................................. 2" inlets, 2" outlet

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature . ..................... 180°F (82°C)

Temperature Adjustment Range .......................... 60 - 95°F (15 - 35°C)

Factory Set Temperature* .................................... 85°F (29°C)

Bypass Flow Rate at 30psid*

ETV200

.............................................. 30 gpm (114 lpm)

ETV400

.............................................. 50 gpm (189 lpm)

ETV500

.............................................. 81 gpm (307 lpm)

Maximum Flow with Cold Water Shutoff* .......... 0.5 gpm (1.9 lpm)

Listing ........................................................................ ASSE 1071

* When tested under conditions specified in ASSE 1071 Standard

Specifications

n

HYDROGUARD

®

XP

Emergency Tempering Valve

with Cold Water Bypass

Technical Instructions

Capacity

n

Flow Capacity at 85°F (29.4°C)

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

15psi

20psi

30psi

45psi

60psi

to ASSE 1071

(34 kPa)

(69 kPa)

(103 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

ETV200

3.0 gpm

6

13.4 gpm

19.0 gpm

23.2 gpm

26.8 gpm

32.9 gpm

40.2 gpm

46.5 gpm

11.4 lpm

50.7 lpm

71.9 lpm

87.8 lpm

101.4 lpm

124.5 lpm

152.2 lpm

176.0 lpm

ETV400

3.0 gpm

15.2

34.0 gpm

48.1 gpm

58.9 gpm

68.0 gpm

83.2 gpm

102.0 gpm

118.0 gpm

11.4 lpm

128.7 lpm

182.0 lpm

223.0 lpm

257.4 lpm

315.0 lpm

386.1 lpm

446.7 lpm

ETV500

3.0 gpm

21.8

48.7 gpm

68.9 gpm

84.4 gpm

97.5 gpm

119.4 gpm

146.2 gpm

168.9 gpm

11.4 lpm

184.3 lpm

260.8 lpm

319.5 lpm

369.1 lpm

452.0 lpm

553.4 lpm

639.4 lpm

IS-P-ETV200_400_500

Advanced Thermal Activation

FAILURE TO COMPLY WITH PROPER INSTALLATION

AND MAINTENANCE INSTRUCTIONS COULD

CONTRIBUTE TO THE VALVE FAILURE, RESULTING IN

INJURY AND DEATH.

TO ENSURE THE ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:

• Properly size each valve based on the individual

application.

• Properly design the recirculation system to minimize

pressure and temperature variations.

• Check outlet temperature to ensure it does not

exceed 110°F (43°C). Make sure temperature limit

stop is properly reset to maximum 110°F (43°C) fol-

lowing valve maintenance or repair. Tampering with

limit stop in any way may result in scalding tempera-

ture causing serious bodily harm and/or death.

Periodic Inspection/Maintenance: OPERATION OF

EMERGENCY VALVES AND FIXTURES SHOULD BE

TESTED WEEKLY PER ANSI Z358.1. In addition con-

duct an annual maintenance program by a licensed

plumber or a qualified service technician to ensure

proper operation of the critical components. Regular

checking and cleaning of the thermostat assembly

assures proper product function. Corrosive water

conditions, temperatures over 210°F, unauthorized

adjustments or repair could render the valve ineffec-

tive for the service intended.

WARNING

!

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use

information can result in death, serious personal

injury, property damage, or damage to the

equipment.
Keep this Manual for future reference.