Powers HydroGuard Lead Free Water Tempering with Automatic Balancing System User Manual

Lead free, Technical instructions

Advertising
background image

Lead Free

*

HydroGuard

®

Water Tempering

with Automatic Balancing System

Technical Instructions

IS-P-RECIRCULATING_LOOP

Maximum Operating Pressure 125psi (861 kPa)
Maximum Hot Water Temperature 200°F (93°C)
Minimum Hot Water Supply Temp 5°F (3°C) Above Set

Point**

Hot Water Inlet Temperature Range 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range 40 - 80°F (4 - 27°C)
Temperature Adjustment Range ***
Standard

90 - 160°F (32 - 71°C)

Low

60 - 90°F (16 - 32°C)

Listing - Valve Only ASSE 1017
Certified - Valve Only CSA B125

** With Equal Pressure
*** Note: Low limit cannot be less than the cold water temperature. For best operation,

hot water should be at least 5°F (3°C) above desired set point.

Specifications

n

Description

n

The HydroGuard

®

Lead Free

*

water tempering and recirculation loop is an eco-

nomical way to provide a safe, balanced system for stand-alone master tempering

valves The system monitors return line temperature and automatically directs

water to the cold side of the tempering valve (if within set point) or to the hot water

source (below set point) This is accomplished with Powers exclusive automatic

balancing valve (ABV), featuring paraffin-based, advanced actuation technology

Capacity

n

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

20psi

30psi

45psi

60psi

to ASSE 1017

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

LFMM431

3 gpm

6 32

14 gpm

20 gpm

28 gpm

35 gpm

42 gpm

49 gpm

11 lpm

53 lpm

76 lpm

106 lpm

132 lpm

159 lpm

185 lpm

LFMM432

4 gpm

9 49

21 gpm

30 gpm

42 gpm

52 gpm

64 gpm

74 gpm

15 lpm

80 lpm

114 lpm

159 lpm

197 lpm

242 lpm

280 lpm

LFMM433

5 gpm

16 44

37 gpm

52 gpm

74 gpm

90 gpm

110 gpm

127 gpm

19 lpm

140 lpm

197 lpm

280 lpm

341 lpm

416 lpm

481 lpm

LFMM434

7 gpm

21 50

48 gpm

68 gpm

96 gpm

118 gpm

144 gpm

167 gpm

26 lpm

182 lpm

257 lpm

363 lpm

447 lpm

545 lpm

632 lpm

LFMM435

10 gpm

31 00

69 gpm

98 gpm

139 gpm

170 gpm

208 gpm

240 gpm

38 lpm

261 lpm

371 lpm

526 lpm

644 lpm

787 lpm

908 lpm

LFSH1432

1 gpm

8 54

19 gpm

27 gpm

38 gpm

47 gpm

57 gpm

66 gpm

4 lpm

72 lpm

102 lpm

144 lpm

178 lpm

216 lpm

250 lpm

LFSH1434

1 gpm

19 00

42 gpm

60 gpm

85 gpm

104 gpm

127 gpm

147 gpm

4 lpm

159 lpm

227 lpm

322 lpm

394 lpm

481 lpm

556 lpm

LFSH1435

5 gpm

30 00

67 gpm

95 gpm

134 gpm

164 gpm

201 gpm

232 gpm

19 lpm

254 lpm

360 lpm

507 lpm

621 lpm

761 lpm

878 lpm

LEAD FREE

*

TO ENSURE THE ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:

• Properly size each valve based on the individual

application

• Properly design the recirculation system to minimize

pressure and temperature variations

• Conduct an annual maintenance program to ensure

proper operation of all critical components

THIS VALVE MUST BE USED IN CONJUNCTION WITH

TEMPERATURE ACTUATED POINT-OF-USE DEVICES

THAT COMPLY WITH ASSE 1016, 1069, OR 1070.

FAILURE TO COMPLY WITH PROPER INSTALLATION

INSTRUCTIONS COULD CONTRIBUTE TO VALVE

FAILURE, RESULTING IN IN JURY OR DEATH.

WARNING

!

*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

Please read and retain these instructions.

WARNING

!

Need for Periodic Inspection: Periodic inspection by a licensed contractor is

recommended Corrosive water conditions, temperatures over 200°F, unauthor-

ized adjustments or repair could render the valve ineffective for service intend-

ed Regular checking and cleaning of thermostat assembly helps to assure

maximum life and proper product function Frequency of cleaning depends

upon local water conditions