Powers PowerStation XP Single and Multi-Valve Series - Double Valve 0.5 - 271 gpm User Manual

Technical instructions

Advertising
background image

Description

n

Capacity

n

Two Valve PowerStation

Supply Fixture

Capacity up to 271 gpm @ 45psi

Technical Instructions

IS-P-SF-2VPS

Advanced Thermal Activation

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature ...................... 200°F (93°C)

Minimum Hot Water Supply Temp.* ................... 5°F (3°C) Above Set Point

Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)

Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)

Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)

Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)

Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125

* With Equal Pressure
** Minimum flow when 2VPS is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.

Specifications

n

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

20psi

30psi

45psi

60psi

to ASSE 1017

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

MM431HL and

LFMM431HL

0.5 gpm

9.70

22 gpm

31 gpm

43 gpm

53 gpm

65 gpm

75 gpm

1.89 lpm

83 lpm

117 lpm

163 lpm

201 lpm

246 lpm

284 lpm

MM432HL and

LFMM432HL

0.5 gpm

13.00

29 gpm

41 gpm

58 gpm

66 gpm

87 gpm

93 gpm

1.89 lpm

110 lpm

155 lpm

220 lpm

250 lpm

329 lpm

352 lpm

MM433HL and

LFMM433HL

0.5 gpm

19.80

44 gpm

63 gpm

86 gpm

108 gpm

133 gpm

153 gpm

1.89 lpm

167 lpm

238 lpm

326 lpm

409 lpm

503 lpm

579 lpm

MM434HL and

LFMM434HL

0.5 gpm

24.90

56 gpm

79 gpm

111 gpm

136 gpm

167 gpm

193 gpm

1.89 lpm

212 lpm

299 lpm

420 lpm

515 lpm

632 lpm

731 lpm

MM435HL and

LFMM435HL

3.0 gpm

27.70

62 gpm

88 gpm

124 gpm

152 gpm

186 gpm

215 gpm

11.0 lpm

235 lpm

333 lpm

469 lpm

575 lpm

704 lpm

814 lpm

SH1432DV and

LFSH1432DV

2 gpm

27.40

61 gpm

87 gpm

123 gpm

150 gpm

184 gpm

213 gpm

8 lpm

231 lpm

329 lpm

466 lpm

568 lpm

697 lpm

806 lpm

SH1434DV and

LFSH1434DV

2 gpm

37.40

84 gpm

118 gpm

167 gpm

205 gpm

251 gpm

290 gpm

8 lpm

318 lpm

447 lpm

632 lpm

776 lpm

950 lpm

1098 lpm

SH1432HL and

LFSH1432HL

1 gpm

30.00

67 gpm

95 gpm

134 gpm

164 gpm

201 gpm

232 gpm

4 lpm

254 lpm

360 lpm

507 lpm

621 lpm

761 lpm

878 lpm

SH1434HL and

LFSH1434HL

1 gpm

40.40

90 gpm

128 gpm

181 gpm

221 gpm

271 gpm

313 gpm

4 lpm

341 lpm

485 lpm

685 lpm

837 lpm

1026 lpm

1185 lpm

WARNING: TO ENSURE THE

ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS

ESSENTIAL TO:

• Properly size each valve based on the indi-

vidual application.

• Properly design the recirculation system to

minimize pressure and temperature variations.

• Conduct an annual maintenance program to

ensure proper operation of all critical com-

ponents.

THIS VALVE MUST BE USED IN

CONJUNCTION WITH TEMPERATURE

ACTUATED POINT-OF-USE DEVICES THAT

COMPLY WITH ASSE 1016, 1069, OR 1070.

FAILURE TO COMPLY WITH PROPER

INSTALLATION INSTRUCTIONS COULD

CONTRIBUTE TO VALVE FAILURE, RESULTING

IN IN JURY OR DEATH.

!

Powerstation

is a complete, fully assembled water tempering system, designed to

provide safe water throughout commercial and institutional facilities. Powerstation

features the HydroGuard

®

LM490 or LFLM490, HydroGuard

®

XP MM430 or LFMM430,

and SH1430 or LFSH1430 Master Tempering Series valve which utilize paraffin-based

actuation technology to sense and to adjust outlet temperature. Each Powerstation

is mounted on heavy-duty, welded struts and factory tested as a complete system.

Each Powerstation

includes an engineer specified circulator, GFCI outlet, combination

temperature/pressure gauges and Powers' triple-duty checkstops. Optional equipment

includes an Aquastat and/or Powers' exclusive automatic balancing valve and a internal

bypass loop for and easy set-up.

Advertising