Powers PowerStation XP Single and Multi-Valve Series - Single Valve 1 - 208 gpm User Manual

Technical instructions

Advertising
background image

Description

n

Capacity

n

Single Valve PowerStation

Supply Fixture

Capacity up to 208 gpm@45psi

Technical Instructions

IS-P-SF-SVPS

PowerStation

is a complete, fully assembled water tempering system, designed

to provide safe water throughout commercial and institutional facilities.

PowerStation

features the HydroGuard

®

XP MM430, LFMM430 or SH1430,

LFSH1430 master tempering series valve which utilize paraffin-based actuation

technology to sense and adjust outlet temperature. Each PowerStation

is

mounted heavy-duty, welded struts and factory tested as a complete system.

Each PowerStation

includes an engineer specified circulator, GFCI outlet,

combination temperature/pressure gauges and Powers' triple-duty checkstops.

Optional equipment includes an Aquastat and/or Powers' exclusive automatic

balancing valve and an internal bypass loop for easy set-up.

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature ...................... 200°F (93°C)

Minimum Hot Water Supply Temp*. ..................... 5°F (3°C) Above Set-Point

Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)

Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)

Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)

Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)

Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125

* With Equal Pressure
** Minimum flow when PowerStation™ is installed at or near hot water source recirculating
tempered water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation,
hot water should be at least 5°F (3°C) above desired set point.

Specifications

n

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

20psi

30psi

45psi

60psi

to ASSE 1017

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

MM431 and

LFMM431

3 gpm

6.32

14 gpm

20 gpm

28 gpm

35 gpm

42 gpm

49 gpm

11 lpm

53 lpm

76 lpm

106 lpm

132 lpm

159 lpm

185 lpm

MM432 and

LFMM432

4 gpm

9.49

21 gpm

30 gpm

42 gpm

52 gpm

64 gpm

74 gpm

15 lpm

80 lpm

114 lpm

159 lpm

197 lpm

242 lpm

280 lpm

MM433 and

LFMM433

5 gpm

16.44

37 gpm

52 gpm

74 gpm

90 gpm

110 gpm

127 gpm

19 lpm

140 lpm

197 lpm

280 lpm

341 lpm

416 lpm

481 lpm

MM434 and

LFMM434

7 gpm

21.50

48 gpm

68 gpm

96 gpm

118 gpm

144 gpm

167 gpm

26 lpm

182 lpm

257 lpm

363 lpm

447 lpm

545 lpm

632 lpm

MM435 and

LFMM435

10 gpm

31.00

69 gpm

98 gpm

139 gpm

170 gpm

208 gpm

240 gpm

38 lpm

261 lpm

371 lpm

526 lpm

644 lpm

787 lpm

908 lpm

SH1432 and

LFSH1432

1 gpm

8.54

19 gpm

27 gpm

38 gpm

47 gpm

57 gpm

66 gpm

4 lpm

72 lpm

102 lpm

144 lpm

178 lpm

216 lpm

250 lpm

SH1434 and

LFSH1434

1 gpm

19.00

42 gpm

60 gpm

85 gpm

104 gpm

127 gpm

147 gpm

4 lpm

159 lpm

227 lpm

322 lpm

394 lpm

481 lpm

556 lpm

SH1435 and

LFSH1435

5 gpm

30.00

67 gpm

95 gpm

134 gpm

164 gpm

201 gpm

232 gpm

19 lpm

254 lpm

360 lpm

507 lpm

621 lpm

761 lpm

878 lpm

Advanced Thermal Activation

WARNING: TO ENSURE THE

ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS

ESSENTIAL TO:

• Properly size each valve based on the indi-

vidual application.

• Properly design the recirculation system to

minimize pressure and temperature variations.

• Conduct an annual maintenance program to

ensure proper operation of all critical com-

ponents.

THIS VALVE MUST BE USED IN

CONJUNCTION WITH TEMPERATURE

ACTUATED POINT-OF-USE DEVICES THAT

COMPLY WITH ASSE 1016, 1069, OR 1070.

FAILURE TO COMPLY WITH PROPER

INSTALLATION INSTRUCTIONS COULD

CONTRIBUTE TO VALVE FAILURE, RESULTING

IN IN JURY OR DEATH.

!

Advertising