Powers PowerStation XP Single and Multi-Valve Series - Triple Valve 1 - 416 gpm User Manual

Technical instructions

Advertising
background image

Description

n

Capacity

n

Triple Valve PowerStation

Capacity up to 416 gpm

Technical Instructions

IS-P-SF-TVPS

Advanced Thermal Activation

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature ...................... 200°F (93°C)

Minimum Hot Water Supply Temp.* ................... 5°F (3°C) above set point

Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)

Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)

Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)

Temperature Adjustment Range *** ................... 90 - 160°F (32 - 71°C)

Listing/Compliance (Valves only) .......................... ASSE 1017, CSA B125

* With Equal Pressure
** Minimum flow when Hi/Lo is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.

Specifications

n

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

20psi

30psi

45psi

60psi

to ASSE 1017

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

SH1434TV and

LFSH1434TV

1 gpm

62.00

139 gpm

196 gpm

277 gpm

340 gpm

416 gpm

480 gpm

4 lpm

526 lpm

742 lpm

1049 lpm

1287 lpm

1575 lpm

1817 lpm

PowerStation

is a complete, fully assembled water tempering system,

designed to provide safe water throughout commercial and institutional

facilities. PowerStation

features the HydroGuard

®

XP MM430 or LFMM430

and SH1430 or LFSH1430 master tempering series valves which utilize

paraffin-based actuation technology to sense and adjust outlet temperature.

Each PowerStation

is mounted on heavy-duty, welded struts and factory

tested as a complete system. Each PowerStation

includes an engineer

specified circulator, GFCI outlet, combination temperature/pressure gauges

and Powers' triple-duty checkstops. Optional equipment includes an

Aquastat.

WARNING: TO ENSURE THE

ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS

ESSENTIAL TO:

• Properly size each valve based on the indi-

vidual application.

• Properly design the recirculation system to

minimize pressure and temperature variations.

• Conduct an annual maintenance program to

ensure proper operation of all critical com-

ponents.

THIS VALVE MUST BE USED IN

CONJUNCTION WITH TEMPERATURE

ACTUATED POINT-OF-USE DEVICES THAT

COMPLY WITH ASSE 1016, 1069, OR 1070.

FAILURE TO COMPLY WITH PROPER

INSTALLATION INSTRUCTIONS COULD

CONTRIBUTE TO VALVE FAILURE, RESULTING

IN IN JURY OR DEATH.

!