Powers SH1434 Triple Valve User Manual

Technical instructions

Advertising
background image

Description

n

Table 1 Capacity

n

HydroGuard

®

XP SH1434 & LFSH1434 Triple,

Quad & Six Valve Hi/Lo Supply Fixture

Technical Instructions

IS-P-SF-SH1434-TV_QV_6V

Advanced Thermal Activation

Powers' HydroGuard

®

XP Series SH1434 & LFSH1434 Triple, Quad and Six Valve

Hi/Lo's are fully assembled, factory tested systems, designed to provide safe

water throughout commercial and institutional facilities. Each consists of MM434

or LFMM434 and SH1434 or LFSH1434 Master Tempering Valves which utilize par-

affin-based actuation technology to sense and adjust outlet temperature. Each

system includes a PRV, ball valves, pressure/temperature gauges and Powers'

triple-duty check stops and are supported by heavy-duty welded struts. Optional

equipment includes cabinets and/or Powers' AquaSentry

®

2 high-temperature

alarm system. (Not available with LFSH1434 Series).

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature ...................... 200°F (93°C)

Minimum Hot Water Supply Temp* .................... 5°F (3°C) Above Set Point

Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)

Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)

Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)

Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)

Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125

*With Equal Pressure
**Minimum flow when Hi/Lo valve is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
***Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.

Specifications

n

Operation

n

The Triple, Quad and Six Valves Hi/Lo feature one low capacity valve that works in

parallel with multiple high capacity valves. During low demand, the low capacity

valve handles the load requirements. As the load demand increases, the pres-

sure reducing valve, which is set at a certain pressure differential, will open and

allow flow through the high capacity valves to assist the low capacity valve in

meeting the increased load requirements.

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

20psi

30psi

45psi

60psi

to ASSE 1017

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

SH1434TV and

LFSH1434TV

1 gpm

62.0

139 gpm

196 gpm

277 gpm

340 gpm

416 gpm

480 gpm

4 lpm

526 lpm

742 lpm

1049 lpm

1287 lpm

1575 lpm

1817 lpm

SH1434QV and

LFSH1434QV

1 gpm

83.3

186 gpm

263 gpm

373 gpm

456 gpm

559 gpm

645 gpm

4 lpm

704 lpm

996 lpm

1412 lpm

1726 lpm

2116 lpm

2442 lpm

SH1434-6V and

LFSH1434-6V

1 gpm

126.3

282 gpm

400 gpm

565 gpm

692 gpm

847 gpm

978 gpm

4 lpm

1067 lpm

1514 lpm

2139 lpm

2620 lpm

3206 lpm

3702 lpm

WARNING: TO ENSURE THE

ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS

ESSENTIAL TO:

• Properly size each valve based on the indi-

vidual application.

• Properly design the recirculation system to

minimize pressure and temperature variations.

• Conduct an annual maintenance program to

ensure proper operation of all critical com-

ponents.

THIS VALVE MUST BE USED IN

CONJUNCTION WITH TEMPERATURE

ACTUATED POINT-OF-USE DEVICES THAT

COMPLY WITH ASSE 1016, 1069, OR 1070.

FAILURE TO COMPLY WITH PROPER

INSTALLATION INSTRUCTIONS COULD

CONTRIBUTE TO VALVE FAILURE, RESULTING

IN IN JURY OR DEATH.

!