Powers 1430 Series HiLo Master Mixing Valve User Manual

Technical instructions, Hi/lo master mixing valves

Advertising
background image

The Hydroguard thermostatically blends hot and cold water to deliver mixed water at the
desired temperature, quickly compensating for temperature variations due to changes in
inlet temperature, pressure or flow, and reduces flow upon water supply failure.
The 1430’s delivery temperature will hold to within ±5°F (± 2.7°C) when tested in accor-
dance to ASSE 1017.

Operating

Maximum Pressure Differential . . . . . . . . . . . . . . . 100 psi (689 kPa)
Maximum Static Pressure . . . . . . . . . . . . . . . 125 psig (861.25 kPa)
Maximum Hot Water Temperature . . . . . . . . . . . . . . . . 200°F (93°C)
Minimum Hot Water Temperature . . . . 15°F (8°C) Above Set-Point
Minimum Flow: 1432 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 gpm **

1434 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.0 gpm **

Temperature Adjustment Range*. . . . . . . 40°F (4°C) - 160°F (71°C)
Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017
Certified . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CSA B125

Note: *Low limit cannot be less than the cold water temperature. For best
operation, hot water should be at least 15

°

F (8

°

C) above desired set point.

**Minimum flow at which valve will control to ASSE 1017 requirements.

TECHNICAL INSTRUCTIONS

1432/1434 Hydroguard

®

Hi/Lo

Master Mixing Valves

DESCRIPTION

SIZING

SPECIFICATIONS

WARNING: TO INSURE THE ACCURATE AND RELIABLE OPERATION OF THIS
PRODUCT, IT IS ESSENTIAL TO:
• Properly size each valve based on the individual application.

• Properly design the recirculation system to minimize pressure and temperature varia-

tions.

• Conduct an annual maintenance program to insure proper operation of all critical

components.

FAILURE TO COMPLY WITH PROPER INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING IN INJURY OR DEATH.

Table A, Capacity Table, presents the Hydroguard discharge capacity in gpm and I/m for various pressure drops across the valves
(the difference between the lowest inlet pressure and the discharge pressure at the Hydroguard).

1432 Hydroguard Valve

Typical Flow
Hot and cold water supplies enter Hydroguard at indicated ports, (see Figure 1) then
flow past their respective balanced poppet plug and seats. Next, hot and cold water
flow is directed to the mixing chamber where the thermostatic motor is located.

Temperature Change
With a rise in discharge temperature due to pressure or temperature fluctuation on
the inlet, the actuator expands, decreasing flow of hot water. The reverse occurs
with a drop in discharge temperature.

Responses
Temperature adjustment screw moves the actuator/poppet to the desired discharge
temperature.

• Cold water supply failure – causes actuator to expand reducing the flow of hot

water.

• Hot water supply pressure failure – causes actuator to contract reducing the flow

of cold water.

Funnel expands or contracts depending on flow rate ensuring maximum heat
transmission to actuator.

OPERATION

Cold

Hot

Cold
Water
Poppet

Hot
Water
Poppet

Expandable
Restrictor

Thermostatic
Actuator

Temper

T

T

ature

Adjusting
Screw

Figure 1

Table A

Flow Capacity in US gpm at 50-50 Mixed Ratio

Model

Min.

Min. Flow

Pressure Drop Across Valves in psi

Flow Rate* to ASSE 1017

5

10

20

30

45

60

75

100

1432

0.5 gpm

1.5 gpm

13.5

18.0

27.0

32.0

40.0

47.0

52.0

60.0

1434

0.5 gpm

5.0 gpm

32.0

45.0

66.0

80.0

100.0

117.0

132.0

152.0

* Minimum flow when Hydroguard is installed at or near hot water source with recirculated tempered water with continuously operating recirculating pump.

Table B

Flow Capacity in lpm at 50-50 Mixed Ratio

Model

Min.

Min. Flow

Pressure Drop Across Valves in kPa

Flow Rate* to ASSE 1017

34

69

138

207

310

414

517

690

1432

1.89 lpm

5.68 lpm

51

68

102

121

151

178

197

227

1434

1.89 lpm

18.92 lpm

121

170

250

302

378

442

500

575

* Minimum flow when Hydroguard is installed at or near hot water source with recirculated tempered water with continuously operating recirculating pump.

TI 1430 HiLo