Powers e420UCM Series Under-the-Counter Thermostatic Tempering Valves User Manual

Technical instructions

Advertising
background image

HydroGuard

®

Series e420

Under-the-Counter Thermostatic Tempering Valve

Technical Instructions

IS-P-e420UCM

Advanced Thermal Activation

Specifications

n

Connections ..................................................................................................................................1/2" NPT Inlets and 1/2" NPT Top Outlet

Capacity (without checkstops) ..................................................................................................4.25 gpm (16.0 L/min)*

....................................................................................................................................................(±0.25 gpm [0.95 L/min])

Maximum Hot Water Supply Temperature ..............................................................................190°F (88°C)

Minimum Hot Water Supply Temperature ..............................................................................10°F (6°C) above set point**

Maximum Operating Pressure ....................................................................................................125 psig (862 kPa)

Temperature Ranges:

Standard ...................................................................................................................................65-115°F (18-46°C)

Low ............................................................................................................................................40-90°F (4-32°C)

High ...........................................................................................................................................120-175°F (49-79°C)

Maximum Static Pressure ...........................................................................................................125 psig (862 kPa)

Minimum Flow: ..............................................................................................................................2.0 gpm (7.6 L/min)

Listing ..............................................................................................................................................ASSE 1070

Shipping Weight ............................................................................................................................5 lbs. (2.3 kg)

* At 45psi differential (310 kPa), with hot water supply between 140°–180°F (60–82°C) and 50/50 mix.
**not applicable to low temperature hot water valves

Description

n

Hydroguard Series e420 Under-the-Counter thermostatic

tempering valves are designed for all applications where the

temperature of generated hot water must be controlled for

safe, economic use. A powerful advanced thermal actuator

quickly senses and compensates for temperature fluctua-

tions induced by water temperature and pressure changes in

the supply line.

Rugged construction features cast brass body and corrosion-

resistant internal components for years of dependable, trou-

ble-free service. Hex socket makes temperature adjustment

quick and easy.

For restricted access control, the Series e420 valve can be

housed in a stainless-steel or white baked enamel steel cabi-

net and can be packaged with solenoid valve(s), checkstops

or other accessories common to Powers’ cabinet supply

offering.

Operation

n

Hot and cold water enter respective ports in the valve and

mix in a chamber containing an advanced thermal actua-

tor (refer to cutaway view). This actuator controls the valve

assembly.

Rotating the adjustment handle repositions the shuttle in the

cartridge assembly to produce the desired temperature. If the

hot or cold supply water temperature or pressure changes,

the thermal actuator will contract or expand. This movement

repositions the shuttle to maintain the desired temperature.

Cold Water Supply

Shuttle

Adjustment
Stem

Advanced thermal Actuator

Shutoff Disk

Cartridge Hot Water Supply