Powers ES400XBY Tempering Valves with Internal & External Cold Water Bypass User Manual

Technical instructions

Advertising
background image

Description

Capacity

HydroGuard

®

Series Tempering Valve

With Internal & External Cold Water Bypass

Technical Instructions

IS-P-ES150-200-400XBY

Powers external bypass emergency tempering valve system consists of Powers ES
Series emergency tempering valve and an independent external cold water bypass.
Under normal operation the valve will thermostatically blend hot and cold water to
deliver tepid water to emergency fi xtures, quickly compensating for temperature
variations due to changes in inlet temperature.
Powers ES Series valves have a dual internal cold water bypass that ensures cold
water fl ow in the event of valve failure or loss of hot water. In many applications,
the internal cold water bypass capacity is adequate to provide proper operation of
the emergency fi xtures.
The external cold water bypass system ensures an adequate supply of cold water
if the primary valve, under a hot water supply loss or other failure mode, lacks the
volume necessary for the proper operation of the emergency fi xture.
Powers external bypass emergency tempering valve system includes a pressure
regulating valve that will open when the outlet pressure decreases to a level that
indicates a lack of water caused by a failure mode.

Specifi cations

Maximum Operating Pressure . . . . . . . . . . . . . . 125psi (861 kPa)

Maximum Hot Water Temperature . . . . . . . . . . 180°F (82°C)

Approach Temperature . . . . . . . . . . . . . . . . . . . . 15°F (8°C) Above Set Point

Temperature Adjustment Range . . . . . . . . . . . . 60 - 95°F (15 - 35°C)

Factory Set Temperature . . . . . . . . . . . . . . . . . . 85°F (29°C)

Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ANSI Z 358-1 1998

Note: Set point cannot be less than the cold water temperature. For best operation, hot and
cold water should be at least 15°F (8°C) from desired set point.

Flow Capacity at 50-50 Mixed Ratio

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

5psi

10psi

20psi

30psi

45psi

60psi

Rate*

(34 kPa)

(69 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

ES150XBY

1.0 gpm

4.0 gpm

6.0 gpm

9.0 gpm

14.0 gpm

17.0 gpm

20.0 gpm

3.8 lpm

15.2 lpm

22.7 lpm

34.1 lpm

53.0 lpm

64.4 lpm

75.8 lpm

ES200XBY

3.0 gpm

15.0 gpm

20.0 gpm

30.0 gpm

36.0 gpm

45.0 gpm

52.0 gpm

11.0 lpm

57.0 lpm

76.0 lpm

113.0 lpm

136.0 lpm

170.0 lpm

197.0 lpm

ES400XBY

3.0 gpm

27.0 gpm

38.0 gpm

54.0 gpm

66.0 gpm

80.0 gpm

92.0 gpm

11.0 lpm

102.0 lpm

144.0 lpm

203.0 lpm

249.0 lpm

305.0 lpm

352.0 lpm

Advanced Thermal Activation

*Minimum fl ow when emergency bypass valve is installed at or near hot water source with recir-
culating tempered water with a properly sized continuously operating recirculating pump.

Cold Water Bypass Capacity

*

ES150XBY . . . . . . . . . . . . . . . . . . . . . . . . . 10.0 gpm (37.8 lpm) @ 30psi (207 kPa)
ES200XBY . . . . . . . . . . . . . . . . . . . . . . . . 36.0 gpm (136.3 lpm) @ 30psi (207 kPa)
ES400XBY . . . . . . . . . . . . . . . . . . . . . . . . 52.0 gpm (196.8 lpm) @ 30psi (207 kPa)

* Flow capacity measured with 60psi (414 kPa) cold water supply pressure.

WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:

• Properly size each valve based on the indi-

vidual application.

• Properly design the recirculation system to

minimize pressure and temperature variations.

• Conduct an annual maintenance program to

ensure proper operation of all critical com-
ponents.

FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.

!