tekmar 076 Indoor Sensor User Manual

Data brochure, D 076, Indoor sensor 076

Advertising
background image

1 of 4

© 2007

D 076 - 05/07

- Data Brochure

Indoor Sensor 076

D 076

05/07

To remove the 076 front cover, place a small screwdriver
or similar object into the small hole located in the top
of the 076 enclosure. Push the screwdriver against the
plastic flap and pull the top of the front cover so that it
pivots around the bottom edge of the mounting base.

Installation - Indoor Sensor 076

The tekmar Indoor Sensor 076 includes a 10kΩ thermistor which provides accurate
measurement of the indoor temperature. The 076 can be mounted directly on the wall using
two #6-1” screws. The small size of the 076 makes this sensor visually appealing and less
noticeable on the wall. The 076 can be connected to a 10k Room Temperature Unit (RTU)
for remote temperature sensing.

STEP ONE

GETTING READY

Check the contents of this package. If any of the contents listed are missing or damaged,
please contact your wholesaler or tekmar sales representative for assistance.

Type 076 includes: •• One Indoor Sensor 076 •• One Data Brochure D 076

STEP TWO

REMOVING THE FRONT COVER

NOTE: The temperature sensor (thermistor) is built into the 076 enclosure.

STEP THREE

MOUNTING THE INDOOR SENSOR

Small slot for
screwdriver

Top View of Indoor Sensor

•• The Indoor Sensor should be installed on an interior

wall of the desired zone to be controlled. Do not
mount the 076 in a location that may be affected
by localized heat sources or cold drafts. It may be
necessary to install a draft barrier and / or insulation
behind the enclosure in order to prevent air from
blowing through the wiring hole and affecting the
Sensor reading.

•• For surface mounting, mount the Indoor Sensor

directly to the wall using two #6-1” screws. The
screws are inserted through the mounting holes
and must be securely fastened to the wall. If
possible, at least one of the screws should enter
a wall stud.

Advertising