Settings, Program mode, Display mode power on – tekmar 152 Two Stage Setpoint Control User Manual

Page 3: Operating mode, Max. 24 volts

Advertising
background image

Electrical connections

Power and output connections — Caution, Maximum 24 Volts A.C. or D.C.

Connect: — the power supply to terminals

C — R +(1 and 2)

— the heating/cooling device circuit 1 to terminals

Relay 1 (3 and 4)

— the heating/cooling device circuit 2 to terminals

Relay 2 (5 and 6)

Sensor connection(s) — Caution, voltage is never applied to these terminals

Connect:

Sensor 071 to terminals

S1 Sen and Com (7 and 8)

Sensor 071 to terminals

S2 Sen and Com (7 and 9) Optional

3

Test the sensor (s)

This test must be performed

before power is applied to the control and before a sensor is connected to the terminal strip. Test

the sensor(s) according to the instructions printed in the enclosed Data Brochure D 070.

Test the power supply

• Ensure that the wires from the power supply transformer are not touching each other, any other wires or ground. Turn on the

power and, using an AC voltmeter, you should measure between 20 and 28 volts at the secondary side of the transformer.

• Turn off the power and complete the electrical connections to the terminal strip of the control.

The digital display on the Two Stage Setpoint Control 152 has the following uses:

• To display the actual temperature(s) during normal operating mode.
• To allow the user to view and program the various control settings.
• To display control operation. ("HEAT" display element comes on when either relay closes to operate a heat source and "COOL"

display element comes on when either relay closes to operate a cooling device.)

• To display sensor faults. (Display will show "Err" when a sensor is either disconnected, short circuited or out of temperature range.)
• To display program faults. (Display will show "Prgm Err" when the “Heat/Cool” single sensor mode is incorrectly programmed.)

The following diagram illustrates how to operate the keypad buttons in order to view settings and program the control.

Do not apply

power here

24V

power

supply

Heating/Cooling

device circuit #1

Heating/Cooling

device circuit #2

1

C–

2

R+

3

4

10A

10A

Relay 1

Relay 2

5

6

7

Com

Sen

S1

Sen

S2

Sen

8

9

Sensor

#1 (071)

Sensor

#2 (071)

Power

Settings

The control automatically goes back to operating mode when the buttons are left alone for 20 seconds

The control automatically goes back to operating mode when the buttons are left alone for 20 seconds

Item

Item

Item

Item

Item

Item

Push or to

change Differential

Push or to

change Delay

Push or to select between

Heating or Cooling operation

Item

Push or to

change Setpoint

Item

Push or to

change Setpoint

Item

Push or to

change Differential

Item

Item

Push or to

change Delay

Item

Push or to select between

Heating or Cooling operation

Item

Push or to select between

Fahrenheit or Celsius scales

2 Sensors

Dip Switch Up

If two sensors are are in use.

PROGRAM MODE

Pushing the "Item" button,

"PRGM 2" appears, and the

Setpoint (2) pointer will

flash.

PRGM

F

Setpoint

When the control is

powered-up, all display

elements turn on.

DISPLAY MODE

POWER ON

When in operating mode,

the actual sensor

temperature(s) are

displayed.

After approximately 5 seconds, the control

automatically goes into operating mode.

OPERATING MODE

Push and Release the

"Item" button. The display

will toggle between sensor

1 and 2.

1

Delay

1

PRGM

COOL

PRGM

F

Differential

2

PRGM

F

C

1

Push all three buttons

at the

same time. "PRGM 1" will

appear and the Setpoint (1)

pointer will flash. The control

will be in programming mode.

Pushing the "Item"

button changes the

flashing pointer to

Differential (1)

Pushing the "Item" button

changes the flashing pointer

to Delay (1)

Pushing the "Item" button

allows Heating or Cooling (1)

operation to be selected

Pushing the "Item" button

allows the Fahrenheit or

Celsius scale to be

selected

Pushing the "Item" button

changes the flashing pointer

to Differential (2)

Pushing the "Item" button

changes the flashing pointer

to Delay (2)

Pushing the "Item" button

allows Heating or Cooling

(2) operation to be selected

Push and Hold the "Item"

button. The programmed

Setpoint 1 and then

Setpoint 2 will be displayed.

Push and Hold the

button. The programmed

Differential 1 and then

Differential 2 will be

displayed.

Push and Hold the

button. The programmed

Delay 1 and then Delay 2

will be displayed.

Setpoint

F

1

HEAT

COOL

F

C

1

PRGM

F

Differential

1

PRGM

Delay

1

PRGM

Delay

2

PRGM

HEAT

COOL

2

F

Differential

1

PRGM

HEAT

COOL

F C

Setpoint

Differential

Delay

1

2

PRGM

F

Setpoint

2

F

2

F

HEAT

COOL

COOL

COOL

Max. 24

Volts

Advertising