tekmar 360 Mixing Control User Manual

Data brochure, D 360, Mixing control 360

Advertising
background image

- Data Brochure

Mixing Control 360

D 360

03/09

1 of 20

© 2009

D 360 - 03/09

The Mixing Control 360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or
setpoint operation. The control uses a floating action mixing valve to regulate the supply water temperature, while protecting the boiler
against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.

Additional Functions Include:
• Quick Setup for easy installation and programming of control

• User comfort adjustment to increase or decrease building space

temperature

• Advanced settings to fine-tune building requirements

• Boiler Control for improved energy savings

• Powered mixing system pump output

• Optional indoor sensor for room air temperature control

• Test sequence to ensure proper component operation

• Setback input for energy savings

• 120 V (ac) power supply

• CSA C US certified (approved to applicable UL standards)

Output

Mixing Valve &

Actuating Motor

Input

Universal Sensor

Included

Input

Universal Sensor

Included

Input

tekmar Timer

Optional

Input

Outdoor Sensor

Included

Input

Indoor Sensor

Optional

Output

Boiler

Output

Mixing System

Pump

Input

120 V (ac) Power

Supply

Input

Mixing Demand

Signal

L

N

N

Opn Cls

Sw

Sys

Pmp

R

R

C

UnO Com Boil Mix Com Out Indr

1 2

3

5

9 10 11

4

6

7 8

12 13 14 15 16 17 18

Mixing Control 360

Floating Action

Do not apply power

Signal wiring must be

rated at least 300 V.

Mixing

Power

Boiler

Demand

Test

Terminal

Unit

Motor

Speed

Open Close Mixing

Demand

Made in Canada by

tekmar Control Systems Ltd.

tektra 912-02

Power:

120 V 50/60 Hz 1300 VA

Floating Output:

24 V (ac) 0.34 A 8 VA

Relays:

240 V (ac) 10 A 1/3 hp

Demand:

20 to 260 V (ac) 2 VA

H1

170E

Item

Powered Output

ROOM

-

Set to desired room temp.

OUTDR DSGN - Set to coldest (design)

outdoor temp.
Terminal Unit

Set to

High Mass Radiant -------

1

Low Mass Radiant -------

2

Fan Coil ------------------

3

Convector ----------------

4

Radiator ------------------

5

Baseboard ---------------

6

Refer to brochure for more information

Installer Instructions

To increase or decrease the

building temperature:

• Press the Item, , buttons

simultaneously for 1 sec. to

enter the ADJUST menu

• Use the, , buttons to

adjust the ROOM setting

Display defaults back to VIEW

menu after 20 sec.

Meets Class B:

Canadian ICES

FCC Part 15

Dat

e Code

Note:
Mixing demand must
be powered with 20 to
260 V (ac) before the
boiler is able to fire.