tekmar 363 Universal Reset Control User Manuals User Manual

User brochure, U 363, Menu item

Advertising
background image

1 of 4

Copyright © 1999 U 363 -06/99

The tekmar Universal Reset Control 363 has a Liquid Crystal Display (LCD) and
four push buttons (

Menu, Item, , ) which are used to view and adjust the settings.

Menu

All of the items displayed by the control are organized into various menus. These menus
are listed on the left hand side of the display (Menu Field). To select a menu, use the
Menu button. By pressing and releasing the Menu button, the display will advance to the
next available menu. Once a menu is selected, there will be a group of items that can
be viewed within that menu.

Item

The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the

Item button. Once you have

reached the last available item in a menu, pressing and releasing the

Item button will

return the display to the first item in the selected menu.

Adjust

To make an adjustment to a setting in the control, begin by selecting the appropriate
menu using the

Menu button. Then select the desired item using the Item button. Finally,

use the and/or button to make the adjustment.

Additional information can be gained by observing the Status and Pointers fields of the
LCD. The status field will indicate which of the control’s outputs are currently active. Most
symbols in the status field are only visible when the View Menu is selected.

- User Brochure

U 363

06/99

Universal Reset Control 363

User Interface

!

1

%

DHW

Open / Close
Displays when the actuator is
opening or closing the valve.

Mixing Device Output Scale

Shows output of injection pump
or mixing valve. Arrows show
whether the output is increasing
or decreasing.

Burner
Displays when the boiler relay is
turned on.

Pump
Displays boiler pump 1 and/or
mixing pump 2 is operating.

DHW Pump / Valve
Displays when the DHW pump or
valve is on.

Storage Operation
Displays when the variable speed
driven injection pump is drawing
heat from the storage tank.

Boost
Displays when the control is in
boost after setback.

UnOccupied Mode
Displays when control is in
unoccupied mode.

Occupied Mode
Displays when the control is in
occupied mode.

Override
Displays when the control is in
override mode.

Warning
Displays when an error exists or
a limit has been reached.

Lock - Unlock
Displays whether access levels
are locked or unlocked.

°F, °C, sec, min, hr,

Units of measurement.

Pointer
Displays control operation as
indicated by text.

UnOcc

1 2

Ovr

Close

Open

°

F,

°

C, sec,

min, hr

Occ

The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and
efficiency provided by a hydronic heating system. The control automatically adjusts the boiler and mixed loop
water temperatures that are delivered to the heating system by using an outdoor reset. Outdoor reset increases
the water temperature in the heating system as the outdoor temperature becomes colder. Outdoor reset also
increases the energy efficiency of the heating system by not allowing more heat into the building than the
building normally loses to the outside. Another benefit of outdoor reset is the reduction of indoor temperature
swings - especially in the fall and spring months. The 363 can intelligently integrate indirect fired Domestic
Hot Water (DHW) and tekmar zone controls into the heating system.

Access Level(s) The tekmar Universal Mixing Control 363 has four access levels which are LTD (limited), USER, INST (Installer),
and ADV (advanced). This brochure only covers the LTD (Limited) and USER levels. Only qualified service people should make
adjustments in the INST (Installer) and ADV (advanced) access levels.

Aux

Universal Reset Control 363
Mixing, Boiler & DHW

LR 58223

N R T L / C

R

Menu

Item

°F

1

Vie

2

1

%

Mix Demand

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Minimum

Maximum

DH

Mix Demand

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Minimum

Maximum

Menu

Item

Number Field

Displays the current value
of the selected item

{

Buttons

Selects Menu,
Items and adjusts
settings

1

DHW

View
Adjust
Monitor

Open
Close

2

1

%

Menu Field

Displays the
current menu

Status Field

Displays the
current status of
the control’s
inputs, outputs
and operation

Item Field

Displays an abbreviated
name of the selected item

!

min

sec

Misc

°F°C

Ovr

Schd

hr

Aux

UnOcc

Advertising