Installation, Step one, Step two – tekmar 365 Mixing Control User Manual

Page 7: Step three, Setpoint operation

Advertising
background image

Copyright © D 365 - 06/00

7 of 16

Caution

Improper installation and operation of this control could result in damage to equipment and possibly even personal injury.
It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards.

Step One

Getting ready

Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited Warranty and
Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance.

Type 365 includes:

One Control 365 • One Outdoor Sensor 070 • One Universal Sensor 071
• One Data Brochure D 365 • One Data Brochure D 001 • One Application Brochure A 365
• One Essay E 021

Other information available:

• Essay E 001 • Essay E 002

Read Brochure A 365 and E 021 and select the correct Application for your job.

Note:

Carefully read the details of the Application, and the Sequence of Operation sections in all applicable brochures to ensure that you
have chosen the proper control and understand its functions within the operational requirements of your system. Some applications
feature boiler return protection and require an additional Universal Sensor 071 to be ordered.

Step Two

Mounting of the base

The control should be removed from its base by pressing down on the release clip in the wiring chamber and sliding upwards on
the control. The base is then mounted in accordance with the instructions in the Data Brochure D 001.

Step Three

Rough-in Wiring

All electrical wiring terminates in the control base wiring chamber. It has standard 7/8" (22mm) knock-outs that will accept common
wiring hardware and conduit fittings. Before breaking out the knock-outs, check the wiring diagram and select those sections of
the chamber with common voltages, since the safety dividers will later prevent wiring from crossing between sections.

Power should not be applied to any of the wires during this rough-in wiring stage.

• Install the Outdoor Sensor 070, and the Universal Sensor 071 according to the instructions in the Data Brochure D 001 and

run the wiring back to the control.

Notes on operation of Minimum Return and Maximum Supply functions

At times, the control may be trying to control both the Maximum Supply and Minimum Return temperatures (e.g.. when leaving a
deep setback). When this occurs, the control is programmed to give priority to the Minimum Boiler Return function, and only the
"Min. Return" light will be displayed.

When the control is in WWSD, the "Min. Return" and "Max. Supply" lights will not be displayed.

When using a Return Sensor for Minimum Return protection, it is essential that there always be water flow past the return sensor
whenever there is a heat demand.

See Brochure A 365.

Caution:

The tekmar Mixing Control 365 is an operating control and not certified or intended for use as a primary safety device. Under
normal operating conditions, the control will provide excellent protection against excessive supply temperatures and low
boiler return temperatures; However, if fail-safe protection against either of these conditions is essential then separate
certified safety limit devices should be employed.

Selector Switch = External Heat Demand

Zone Control

Boiler on when 25% open
External Heat Demand

Setpoint

1

2

3

4

Dem Dem

Heat

1

2

Zone Control

Boiler on when 25% open

External Heat Demand

Setpoint

1

2

3

4

+

Setpoint Operation

When the control is in the Setpoint mode, it will control the supply water temperature based on the setting
of the Max./Setpoint dial. The Outdoor Sensor need not be installed and the Occupied, and Heating Curve
dials are inactive. If the control receives an Unoccupied signal, the supply temperature will be controlled
at the setting of the Unoccupied dial. When an optional Boiler Return Sensor 071 is installed, the Minimum
Boiler Return function is activated based on the setting of the "Min. Return" dial.

Selector Switch = Setpoint

Installation

External Heat Demand signal

A heat demand signal is caused by either 24 or 120Vac applied to terminals
Heat Dem — Heat Dem (1 and 2). This signal will activate the control, allowing
it to operate the system to deliver the selected setpoint temperature.

AND/OR

An active (calling for heat) 10 K Zone Control connected
to terminals

Com Sen — 10K Sen (14 and 15).

Reset

Permanent Heat Demand

Indoor Sensor

Boiler on when 10% open

1

2

3

4

Selector Switch = Permanent Heat Demand

12

13

2K

RTU

Com

Sen

16

Sup

Sen

17

Out

Sen

18

19

Com

Ret

Sen

11

10

+

4-20

UnO

Sw

14

Com

Sen

10K

Sen

15

Zone Control

Boiler on when 25% open
External Heat Demand

Setpoint

1

2

3

4

Permanent Heat Demand signal

A heat demand signal is continuously present and the control will continuously operate the system to
deliver the selected setpoint temperature.