The Universal Reset Control 364 is designed to maximize the comfort and efficiency provided by a hydronic heating system. The
control automatically adjusts the boiler and mixed loop water temperatures that are delivered to the heating system by using outdoor
reset. For a mixing device, the 364 can use either a variable speed injection pump or a floating action mixing valve. The mixed water
temperature can be used to supply either a space heating system or a single zone snow melting system. The 364 is capable of
controlling an indirect Domestic Hot Water (DHW) storage tank and / or a setpoint load. The temperature of individual zones can be
controlled by connecting either a conventional thermostat system or a tekmar zone control to the 364. A large Liquid Crystal Display
(LCD) is incorporated in order to view system status and operating information.

• Warm Weather Shut Down (WWSD)
• Manual Override
• Optional DHW Priority
• Remote Display and Adjustment Capabilities

• Test Sequence to Ensure Proper Component Operation
• 120 V (ac) Power Supply
• CSA C US Certified (approved to applicable UL standards)

Additional features include:

Do not apply power

1

Mix

Demand

2 3

Boil

Dem

4

Com
Dem

5

Setp/
DHW

6

Power

N

7

L

8

Prim

P1

9

Boil Sys
Pmp P2

Mix Sys
Pmp P3

DHW

Pmp/Vlv

10 11 12 13 14 15

Boiler

16 17

Pwr

Mix

18

Opn

19

Cls/

Var

20

Com

21

Mix

10K

22

Mix
Ret

23

Mix

Sup

24

Com

25

Boil

Zo In

26

Boil

27

Com

28

DHW

29

Out

30

tN2

Mix Demand

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Min / Max

Melting

Universal Reset Control 364

Mixing, Boiler & DHW

158033

Snow Melting

Mixing Reset

Made in Canada by
tekmar Control Systems Ltd.
tektra 928-01

For maximum heat,
press and hold Test
button for 3 seconds.

not testing
testing
testing paused

off
red
red

Signal wiring must be rated at least 300 V.

Power

120 V ± 10% 50/60 Hz 1300 VA

Relays

240 V (ac) 5 A 1/3 hp, pilot duty 240 VA

Var. Pump

240 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250 V

Demands

20 to 260 V (ac) 2 VA

Menu

Item

Test

Input

Universal Sensor

Optional

Input

tekmar Zone Control,

Slab Sensor, or Indoor Sensor

for mixing zones

Output

Mixing Valve &

Actuating Motor

Output

Var. Speed

Driven Pump

Output

Boiler

Output

DHW Pump

OR

DHW Valve

Output

Boiler

System

Pump

Output

Primary

Pump

Output

Mixing

System

Pump

M

M

Input

120 V (ac)

Power

Supply

Input
Outdoor
Sensor
Included

Input
Universal Sensor
Included

Input
Universal Sensor
Included

Input
Universal Sensor
Optional

Input

Mix

Demand

signal

Input

Boiler

Demand

signal

Input

Setpoint

or DHW

Demand

signal

Input
Remote Start/
Stop Module or
Remote Display
Module (RDM)

7

9

8

Input
Zone
Control
for boiler
zones

70

OR

OR

OR

OR

H1

2

1

0B

Do not apply power

Advertising