tekmar 371 House Control User Manual

Data brochure, D 371, House control 371

Advertising
background image

1

D 371

07/96

The House Control 371 is a microprocessor-based control that provides individual tempera-
ture control for up to 5 zones. Each zone can be either connected to the boiler (hot water) loop
or to the mixing (warm water) loop. The supply water temperature to the zones is modulated
based on both the outdoor temperature and indoor temperature feedback from each of the
zones. This outdoor reset strategy reduces indoor temperature swings and increases system
efficiency. Other energy saving functions include a heating system Warm Weather Shut
Down (WWSD) and the ability to lower indoor temperatures for a night setback period. The
control has an Optimum Start / Stop function which automatically calculates when to bring
each zone out of night setback in order to ensure they are returned to their normal operating
temperatures as the setback period ends. The 371 allows integration of an indirect fired DHW
tank into the system. This helps provide faster DHW tank pick-up times and greater energy
savings. The control can also receive a setpoint demand on either the mixing loop or the boiler
loop for snow melting, hot tubs, or other loads.

Control Strategy ................... pg. 2

Testing the Control ...... pg. 16

Sequence of Operation ........ pg. 6

Error Messages ............ pg. 19

Installation ............................ pg. 10

Technical Data .............. pg. 20

Settings ................................. pg. 14

Limited Warranty .......... pg. 20

House Control 371

- Data Brochure

House Control 371

Five Zones, DHW, Boiler & Mixing

Power

WWSD

Minimum
Boiler

DHW
Demand

System
Pump 1

Boiler

Zone 3

24 hr. Timer

• Dial the desired duration
of the UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.

Start

UnOccupied

Duration

0 = always Occupied
24 = always UnOccupied

Maximum
Supply

Zone 2

Zone 4 /
Open

DHW
Pump

Zone 1 /
Cooling

90

70

50

30

10

%

of full
output

1

2

3

4

Setpoint
Demand

System
Pump 2

Zone 5 /
Close

5

70

°

F

(21

°

C)

40
(4)

100
(38)

UnOccupied

LR 58223

N R T L / C

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

0

12 hrs.

24

6

18

R

House Control 371

Five Zones, DHW, Boiler & Mixing

Test

H1

117 2

Made in Canada by
tekmar Control Systems Ltd.

N

2

3

4

P 1

5

Var.

Pmp

Power

L

Sys

12 13 14 15

130

°

F

Off

165

Min. Boiler

Supply

100

Power
Var. Pump
Relays

120 V 50/60 Hz 1500 VA
240 V 50/60 Hz 2.4 A 1/6 hp, fuse T2.5 A 250 V
120 V (ac) 3.2 A 1/4 hp, pilot duty 240 VA

Power

WWSD

Minimum
Boiler

DHW
Demand

System
Pump 1

Boiler

Zone 3

26 27

25

28 29 30

Do not apply power here

31

23 24

1-2

Com

1

3-5

Com

70

°

F

(21

°

C)

40
(4)

100

(38)

UnOccupied

6

7

8

9 10 11

LR 58223

N R T L / C

R

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

24 hr. Timer

0

12 hrs.

24

6

18

• Dial the desired duration of the
UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.

Start

0.2

2

3.6

1

3

Heating Curve

16 17 18

Com

Sen

RTU

1

RTU

2

Com

Sen

RTU

3

RTU

4

RTU

5

Com

Sen

UnO

Sw

Zo

In

Com

Sen

Boil
Sen

Sup
Sen

22

20 21

Boiler

Pmp

DHW

Setp

Dem Dem

2

3

4

Caution: Signal wiring must be rated at least 300V

Max. Supply / Setpnt

120

170

°

F

220

UnOccupied

Duration

0 = always Occupied
24 = always UnOccupied

Maximum
Supply

Zone 2

Zone 4 /
Open

DHW
Pump

Zone 1 /
Cool

90

70

50

30

10

%

of full
output

1

2

3

4

PRGM

S

T I M E

AMPM

UNOCC

OVR

S

M

W T F

T

1
2

LR 58233

E150539

70

70

70

70

Setpoint
Demand

System
Pump 2

Zone 5 /
Close

5

0.2

2

3.6

1

3

Boiler Heating

Curve

1

P 2

Sys

19

Out

Sen

DHW

5

Opn Cls

M

70

Occ/UnOcc

Permitted

1,2

4

3

Occ. only

5

Setpnt

Boiler

Mixing

1 2 3 4 5 Zo

Off

Zone 1 Heat

Zone 1 Cool

Floating

DHW during UnOcc.

Var. Speed

Optimum Start

Thermal Motor

Zone

M

OR

Input

120 V (ac)

Power

Supply

Input

tekmar Zone

Control

Output

Mixed System

Pump

Output

Boiler

Input

Outdoor

Sensor

Included

Inputs

Universal

Sensors

Included

Input

tekmar RTUs or

Indoor Sensors

Input
Setpoint
Demand signal

Output

Var. Speed

Driven Pump

Output
Zone Valves or Zone
Pumps

Output

DHW

Pump

Input

tekmar

Timer

Output

Boiler System

Pump

Input
DHW
Demand signal

Output
Mixing Valve &
Actuating Motor

Output