tekmar 406 House Control Quick Start User Manual

Page 4

Advertising
background image

4

Product design, software and literature are Copyright ©2014 by
tekmar Control Systems Ltd., A Watts Water Technologies Company

All specifications are subject to change without notice.

Printed in Canada. 406_Q - 02/14.

tekmar Control Systems Ltd., A Watts Water Technologies Company. Head Offi ce: 5100 Silver Star Road,

Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com

Item Field

Range

Description

AUTO,

COOL,

HEAT,

BKUP,

OFF

Default = AUTO

Access: User

Set to:

MODE

AUTO - Automatic heat pump switchover between heating and cooling. Boiler or backup
heat is brought on automatically as needed for DHW/Setpoint loads and space heating.
COOL - Heat pump only operates in cooling mode. Backup heat only operates for
DHW/Setpoint loads.
HEAT - Heat pump only operates in heating mode. Boiler or backup heat is brought on
automatically as needed for DHW/Setpoint loads and space heating.
BKUP - Heat pump is disabled. Boiler or backup heat is brought on automatically as
needed for DHW/Setpoint loads and space heating.
OFF - Heat pump is disabled. Boiler or backup heat is disabled.

T, T+M, T+B, T+MB

Default = T

Access: Installer

Set to:

WATER TEMPERATURE

T - Only a tank loop is configured.
T + B - Tank and boiler loops are configured.
T + M - Tank and mix loops are configured.
T + MB - Tank, mix, and boiler loops are configured.

TANK, BOIL, MIX

Default = TANK

Access: Installer

Set to:

ZONES 1-4

Selects which water temperature the on-board tN2 zones are associated with.
TANK - links the tN2 zones to the tank loop.
BOIL - links the tN2 zones to the boiler loop.
MIX - links the tN2 zones to the mixing loop.
Note: This item is only available when either mix or boil water temperatures have
been selected.

GEO, AIR

Default = GEO

Access: Installer

Set to:

HEAT PUMP SOURCE

Select whether the heat pump is an air-source (AIR) or water-source (GEO) heat pump.

1STG, 2STG, ROT

Default = 1STG

Access: Installer

Set to:

HEAT PUMP TYPE

1STG - operates a single stage heat pump.
2STG - operates a two-stage heat pump.
ROT - operates two heat pumps and rotates them every 48 hours difference in run time.

NONE, AUX, XFER,

VAR

Default = NONE

Access: Installer

Set to:

BACKUP

NONE - No backup heat source is available.
AUX - An auxiliary heat source (electric or instantaneous water heater) is either inside
or in-line with the storage tank.
XFER - A boiler is the backup heat source. Backup heat is transferred from the boiler
loop to the heat pump loop with the transfer pump.
VAR - A boiler is the backup heat source. Backup heat is transferred from the boiler
loop to the tank loop with the variable speed pump.
Note: If boil and mix water temperatures are configured, this item is automatically set
to XFER and is no longer displayed.

1STG,

0-10,

4-20,

EMS1,

EMS2

Default = 1STG

Access: Installer

Set to:

BOILER TYPE

The type of boiler connected to the control.
1STG - single one-stage on-off boiler
0-10 - 0-10 V (dc) modulating boiler
4-20 - 4-20 mA modulating boiler
EMS1 - tekmar boiler staging controls
EMS2 - Viessmann modulating boilers
Note: This item is only available when a boil water temperature has been selected.

Advertising