Switch Settings

Switches are set to “On”
position from the factory, and
do not require changing for
most applications.

1

2

3

4

1 2 3 4

tNt 527

527

One Stage Heat

Made in
Canada

Mmm YYYY

Lo

t # 1

23

45

Mee

ts Class B:

Canadian ICES FCC P

ar

t 1

5

1023-0

1

tN2

1

tN2

2

Switch Se

ttings:

For instructions see brochure
Use at least 65°C conductors

ON

Se

tback

Scene

Lock

No

t used

No

t used

Unlock

Off

Off

1

2

3

4

1 2 3 4

Mmm

Mee

ts Class B:

Switch Se

ttings:

ON

Se

tback

Scene

Lock

No

t used

No

t used

Unlock

Off

Off

Switch Position Action

1

ON

SETBACK
The thermostat follows a programmable setback schedule
as a schedule member if available. Requires the installation
of a Timer 033 to use this feature.

OFF

OFF
The thermostat does not follow a programmable setback
schedule.

2

ON

SCENE
The thermostat responds to changes in the scene (system
wide manual overrides). Requires the installation of a User
Switch 479 to use this feature.

OFF

OFF
The thermostat does not respond to scenes.

3

ON

LOCK ACCESS LEVEL
Locked to ‘User’ access level. Set to Lock when installation
completed.

OFF

UNLOCK ACCESS LEVEL
Unlock to allow ‘User’ and “Installer’ access level. Set to
Unlock during installation process.
tekmarNet

®

reset control must also be set to Unlocked

(Installer access level).

4

ON

Not used

OFF

Not used

The thermostats’s exterior can be cleaned using a damp cloth. Moisten the cloth
with water and wring out prior to wiping the control. Do not use solvents or cleaning
solutions.

Cleaning the Thermostat