tekmar 540 Thermostat Quick Start User Manual

Quick setup guide, Location, Remove mounting base

Advertising
background image

1 of 2

© 2011

Q 540 - 12/11

tekmarNet

®

4 Thermostat 540

Q 540

12/11

Zoning

Replaces: 08/10

Quick Setup Guide

Location

1.

Remove Mounting Base

2.

Install Mounting Base

3.

Wiring

4.

Switch Settings

5.

1

2

3

4

tN4 Wiring Center

or

tN4 Zone Manager

Cooling Equipment

1 Stage

Cooling

1 Stage

Fan

G

Y

R

D

X

Fan

Cooling

tN4

C

W

R

1 2 3 4

tNt 540

54

0

One Stage Heat /
One Stage Cool / One Fan

Mmm YYYY

Lo

t # 1

23

45

Mee

ts Class B:

Canadian ICES FCC P

ar

t 1

5

Power:

24 V ±10% 50/60 Hz 1.8 VA

56 VA fully loaded

Relays:

24 V (ac) 2 A

10

01-0

1

tN4

1

C

2

R

3

W

4

7

G

6

Y

5

Rc

Switch Se

ttings:

For instructions see brochure

Use at least 75°C conductors

Se

tback

Scene

Lock

No

t used

ON

No

t used

Unlock

Off

Off

Switch Position Action

1

ON

SETBACK Allow thermostat to respond to
available schedule. Requires Timer 033.

OFF

OFF No setback schedule response.

2

ON

SCENE Allow thermostat to respond to
scenes. Requires User Switch 479.

OFF

OFF No scene response.

3

ON

LOCK Locked to ‘User’ access level. Set
to Lock when installation completed.

OFF

UNLOCK Unlock to access all settings.
Set to Unlock during installation.

4

ON

Not used

OFF

Not used

Close Thermostat

6.

pivot

tab

Thermostat

Base

Adaptor

Plate 007

Switch

Box

OR

Thermostat

Base

Wall

Exterior

Wall

Interior

Wall

5 feet

1.5 m

Switch
Setting
Location