Adjus t menu – tekmar 543 Thermostat Installation User Manual

Page 8

Advertising
background image

© 2007

D 543 - 08/07

8 of 32

Item Field

Range

Access

Description

OFF, ON

Default = ON

INST

ADV

HEAT 1 PUMP

SECTION

F

Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the heat
is operating.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.

OFF, ON

Default = OFF

INST

ADV

HEAT 1 DELAY

SECTION

F

Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a thermal
motor zone valve to open. Select On for thermal motor,
select Off for zone pump or motorized zone valve.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.

None, CTRL, HrF1,

HrF2, COIL, Con,

RAD, bASE, OTHr

Default = CON

INST

ADV

HEAT 2 TERMINAL

SECTION

E

Select the type of heating terminal for second stage
heat. If NONE is selected, the second stage heat is
disabled.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.

BOIL, MIX1,

MIX2, MIX3

Default = BOIL

ADV

HEAT 2 SOURCE

SECTION

F

Select the tN4 bus on which the second stage
heat zone operates. This setting determines water
temperature and system pump operation.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.

OFF, ON

Default = ON

INST

ADV

HEAT 2 PUMP

SECTION

F

Select whether the system, primary, or mixing pump

on a tN4 System Control must operate while the

second stage heat is operating.
Note: This item is only available when the H2 Terminal

item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,

Radiator, or Baseboard.

OFF, ON

Default = OFF

INST

ADV

HEAT 2 DELAY

SECTION

F

Select whether the system, primary, or mixing pump

on a tN4 System Control is delayed to allow a second

stage heat thermal motor zone valve to open. Select

On for thermal motor, select Off for zone pump or

motorized zone valve.
Note: This item is only available when the H2 Terminal

item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,

Radiator, or Baseboard.

NONE, 1 to 16

Default = NONE

ADV

COOL MEMBER

SECTION

G

Select the cool group of which this thermostat is a
member. Select None if this thermostat is not a cool
group member.
Note: This item is only available when the thermostat
is connected to a tN4 network.

Adjust Menu (3 of 4)

ADJUS

T MENU

Continued on next page.