Delta T Maximum

The Delta T Maximum sets the maximum temperature difference between the mixing return
sensor and the mixing supply sensor. This item is only available if Outdoor Design setting
is set to OFF. If a mixing return sensor is not installed, set this item to OFF.

Outdoor Design Temperature

The Outdoor Design Temperature is the outdoor temperature used in the heat loss calcu-
lation. If the RMB is used in the outdoor reset mode, this item is set to the typical coldest
outdoor temperature. If the RMB is used in the setpoint mode, this item is set to OFF.

Mixing Design Temperature

The mixing design temperature is the supply temperature used in the heat loss calcula-
tion. This is the supply temperature that is required to heat the building when the outdoor
temperature is as cold as the outdoor design temperature. This item is only available if the
Outdoor Design setting is not set to OFF.

Mixing Maximum Temperature

The mixing maximum temperature is the highest temperature that the control is allowed
to use as a mixing target temperature. This item is only available if the outdoor design
setting is not set to OFF.

Mixing Minimum Temperature

The mixing minimum temperature is the lowest temperature that the control is allowed to
use as a mixing target temperature. This item is only available if the outdoor design set-
ting is not set to OFF.

Boiler Minimum Temperature

The boiler minimum temperature item should be set to the lowest water temperature at
which the boiler can operate without causing the boiler fl ue gases to condense. Consult
the boiler manufacturer for recommended minimum boiler supply temperatures. This item
is only available if a boiler sensor is connected to the control.

Warm Weather Shut Down (WWSD)

The warm weather shut down is the outdoor temperature at which the system is shut down.
This item is only available if the outdoor design temperature is not set to OFF.

Units

The units of temperature in which all of the View and Adjust items are viewed in.

The control automatically goes back to the view menu when the buttons are left alone for 20 seconds

All settings will be saved even during power down of the control

T

MAX

ADJUST

F

OUT

DSGN

ADJUST

F

MIX

DSGN

ADJUST

F

MIX

MAX

ADJUST

F

MIX

MIN

ADJUST

BOIL

MIN

ADJUST

F

WWSD

ADJUST

F

ADJUST

F

Advertising