Misc menu testing the control – tekmar 421 Mixing Reset Module User Manual

Page 9

Advertising
background image

9 of 20

© 2007

D 421 - 08/07

Item Field

Range

Access

Description

InS (Installer)

Ad (Advanced)

InS

Ad

ACCESS LEVEL
The access level that is to be used by the control.

Note:

This item is only available when the Lock / Unlock

DIP switch is set to Unlock.

°F, °C

Default = °F

InS

Ad

UNITS
Select temperature units between Fahrenheit and
Celsius.

0 to 24

Ad

BUS 1 DEVICES
Displays the number of devices on bus 1 (Mixing).

OFF, SEL

Ad

FACTORY DEFAULT
Loads the factory defaults when the Up and Down
buttons are held down for 1 second.

421

InS

Ad

TYPE
Displays the type number of this product. The software
version is displayed when the Up button is held.

Misc (Miscellaneous) Menu (1 of 1)

The Miscellaneous Menu Items set control

and display options such as access level and
temperature units.

After the last item, the control returns to the first item in the menu.

MISC MENU

Testing the Control

The control has a built-in test routine that tests the main
control functions. The control continually monitors the
sensors and displays an error message whenever a fault
is found. The individual outputs and relays are tested using
a test sequence.

Test Sequence

Each step in the test sequence lasts 10 seconds.

• Start the test sequence by pressing the Test button.

• Pause the test sequence by pressing the Test button

again. To advance to the next step, press the Test button
again.

• If the test sequence is paused for more than five minutes,

the control exits the entire test routine.

• To advance to a particular step, repeatedly press and

release the Test button to display the appropriate
device.

Advertising