Step 2 - mounting, Step 1 - rough in wiring – tekmar 742 Actuating Motor User Manual

Page 3

Advertising
background image

© 2013

742_D - 10/13

3 of 8

Step 2 - Mounting

Using a Phillips screwdriver, remove the two screws in the corners of the actuator
cover. Remove the cover.
Thread the anti-rotation bolt into one of the threaded holes on the mixing valve.
Do not align the anti-rotation bolt with the actuator motor corner cavity.
Install coupler onto mixing valve stem, ensuring that it is pushed all the way on.
Black coupler: for 3-way valves 710, 711, 712, 713, 714
White coupler: for 4-way valves 720, 721, 722, 723, 724
Install actuator body onto the coupler.




Step 1 - Rough In Wiring

Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following:

24 V (ac/dc) power supply
0-10 or 2-10 V (dc) control signal from control

Strip wire to 3/8" (10 mm) for all terminal connections.


0

.2

.4

.6

.8

1

Screw

Handle

Scale Plate

Actuator Motor

Anti-Rotation Bolt

Coupler

Mixing Valve

Mixing Valve Stem

Corner Cavity

Advertising