Product selection & part number guide, Wiring diagram / battery back up, Contact information – TERRALUX DR88 User Manual

Page 6

Advertising
background image

 

 

6  

TerraLUX D

R

88 Product Specification – Subject to change without notice

 

WWW.TERRALUX.COM

10/01/2014

 

   

Product Selection & Part Number Guide

TerraLUX Inc.

Phone: 303-442-4960

1830 Lefthand Circle

Fax: 866-919-2515

Suite B

[email protected]

Longmont, CO 80501

www.terralux.com

 

 

 

   

 

1  

2  

3  

4  

5  

TLK   -­‐  

DR88A  

-­‐  

A  

242  

40  

DO  

0  

Wiring Diagram / Battery Back Up

Standard

With Battery Back Up Option

The  LED  array  is  divided  in  two  parts.  Each  part  is  
powered  by  a  separate  LED  driver.  One  of  the  two  
drivers  is  connect-­‐ed  to  a  Bodine  ELI-­‐S-­‐20  20W  
Backup  micro  inverter.  Under  normal  conditions,  
both  drivers  are  powered  from  mains  and  the  light  
output  and  distribution  of  the  EM  fixtures  is  identi-­‐

cal  to  the  regular  fixtures.    
In  the  event  of  power  outage,  the  Bodine  Micro  
Inverter  will  power  for  at  least  90  minutes  one  of  the  
2  LED  drivers  that  will  illuminate  50%  of  the  LEDs  
(which  results  in  50%  of  the  total  light  output  of  the  
system).    
This  Bodine  solution  is  UL  924  LISTED,  for  Factory  and  

Field  (retrofit)  installation

 