Large curb small curb roof curb detail, 48e z -- a – Carrier 48EZ(N)-A User Manual

Page 5

Advertising
background image

5

LARGE CURB

SMALL CURB

ROOF CURB DETAIL

Wood nailer*

Roofcurb*

Insulation
(field supplied)

*Provided with roofcurb

Cant strip
field supplied

Roofing material
field supplied

Flashing field
supplied

HVAC unit
base rails

Roofcurb

Sealing
Gasket

HVAC unit
basepan

Anchor screw

A09090

A09415

A09418

C

B

A

F

D

E

G

H

C

B

A

D

E

H

F

G

A09419

UNIT SIZE

CATALOG

NUMBER

A

IN. (mm)

B

IN. (mm)*

C

IN. (mm)

D

IN. (mm)

E

IN. (mm)

F

IN. (mm)

G

IN. (mm)

H

IN. (mm)

Small

CPRFCURB010A00

11 (279)

10 (254)

16 (406)

47.8

(1214)

32.4 (822)

2.7 (69)

30.6 (778)

46.1 (1170)

CPRFCURB011A00

14 (356)

Large

CPRFCURB012A00

11 (279)

14 (356)

43.9

(1116)

42.2 (1072)

CPRFCURB013A00

14 (356)

NOTES:

1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.

IMPORTANT: Do not install large base pan HYBRID HEAT units onto
the small base pan (common curb). The center of gravity on a large base
pan HYBRID HEAT unit could overhang the curb causing an unsafe
condition. Before installing any large base pan unit onto the common

curb, check the “Y” distance in the product literature dimensional drawing
to ensure that “Y” is greater than 14 in. (356 mm). Do not install any large
base pan unit onto the common curb with a “Y” dimension (center of
gravity) less than 14 in. (356 mm).

Fig. 4 -- Roof Curb Dimensions

48E

Z

--

A