Heater maintenance checklist, Important notices – CCI Thermal Technologies CR1 - Trito Corrosion-Resistant Washdown Unit Heater User Manual

Page 2

Advertising
background image

1. Read and follow all instructions in this manual.
2.

Heater is not to be used in hazardous atmospheres where
flammable vapors, gases, liquids or other combustible
atmospheres are present.

3. Heater is to be connected and serviced only by a

qualified electrician.

4. Installation and wiring of the heater must adhere to all

applicable codes.

5. Before opening any enclosures, disconnect the heater

from the power supply. Lock the switch in the “OFF”
position and/or tag the switch to prevent unexpected
power application.

6. The heater is not to be operated with the high-limit

disconnected from the control circuit.

7. The heater is not to be operated if the bulb or capillary

of the high-limit is damaged.

8. Do not operate the heater in atmosphere corrosive to

type 304 stainless steel.

9. Elements get hot during operation. Contact can cause

burns.

10. Use factory replacement parts only.
11. Maximum ambient operating temperature is 40°C

(104°F).

12. Type 4X conduits must be used for field connection in

order to maintain watertightness of the enclosure.

13. Do not operate the heater with the louvers deformed

from their factory preset positions.

14. Wash with water pressure less than 70 psi.
15. Complies with U.S. Coast Guard regulations only when

indicated on heater data plate and when the discharge
grill directs airflow downward.

16. If there are any questions or concerns regarding the

heater, please refer to contact info on page 10.

WARNING:

Disconnect heater from the power supply before opening enclosures, washing or servicing heater.

Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.

This heater should only be serviced by qualified personnel with electrical heating equipment experience.

– 2 –

HEATER MAINTENANCE CHECKLIST

Heater Model: ____________________________ Serial No.: ______________________________
Date of Maintenance: ______________________ Maintenance Done By: ____________________
Comments: ________________________________________________________________________

________________________________________________________________________

PERIODIC (before and as required during heating season)

ANNUAL (before heating season)

IMPORTANT NOTICES

WARNING:

Read and adhere to the following. Failure to do so may result in severe or fatal injury.

2. MECHANICAL

Check for leakage inside the control enclosure. The

electrical enclosure should be dry inside.

Check enclosure seal. Seal should be free of nicks and

cuts.

Check motor shaft bearing play. Replace motor if play

is excessive, or if motor does not run quietly and
smoothly. Bearings are permanently lubricated.

Check fan. Replace immediately if cracked or

damaged.

Check high-limit bulb and capillary. Replace

immediately if damaged.

Check tightness of all hardware. All fasteners must be

tight.

Turn heater on for a minimum of five minutes. Check

for warm air exiting heater through discharge grill.

1. CLEAN (Use water pressure less than 70 psi)

❑ Finned Elements ❑ Motor

❑ Fan

❑ Discharge Grill

❑ Inlet Grill

2. CHECK

❑ All watertight seals for condition and tightness
❑ Motor for smooth, quiet operation

1. ELECTRICAL

Check all terminal connections and conductors.

Tighten loose connections. Conductors with
damaged insulation must be replaced.

Inspect contactor contacts. If badly pitted,

burned or welded shut, replace with factory-
supplied contactor.

Check all watertight fittings. Replace damaged

seals with factory supplied seals.

Check electrical resistance on all load side legs.

Reading should be balanced (±5%).

Photocopy

this page

for reuse.