Code 21

Reset thermistor failure (applies only to installa-

tions having external temperature reset) (alert)

If temperature measured by this thermistor is outside range

of –40 to 240 F (–40 to 116 C), reset function is disabled and
unit controls to normal set point. If temperature returns to
the acceptable range, reset function is automatically en-
abled. The cause of this fault is usually a bad thermistor,
wiring error, or loose connection.
Code 22

Compressor A1 discharge pressure
transducer failure (alert)

Code 23

Compressor B1 discharge pressure
transducer failure (alert)

Code 24

Compressor A1 suction pressure transducer
failure (alert)

Code 25

Compressor B1 suction pressure transducer
failure (alert)

Code 26

Compressor A1 oil pressure transducer failure (alert)

Code 27

Compressor B1 oil pressure transducer failure (alert)

If output voltage of any of these transducers is greater than

5 v, affected circuit shuts down without going through pum-
pout process (Alerts 24-27). Other circuit continues to run.
Reset is automatic if output voltage returns to the acceptable
range, and circuit start-up follows normal sequence. The cause
of this fault is usually a bad transducer or a wiring error.
Code 28

Low transducer supply voltage (alarm)

If transducer supply voltage is less than 4.5 v or greater

than 5.5 v, unit shuts down without going through pumpout
process. Reset is automatic if supply voltage returns to the
acceptable range, and circuit start-up follows normal se-
quence. The cause of this fault is usually a faulty trans-
former or primary voltage is out of range.

LEGEND

C

Contactor

CB

Circuit Breaker

COM, COMM — Communications Bus
CPCS

Compressor Protection

Control Module

CR

Compressor Contactor Relay

DGT

Discharge Gas Thermostat (Optional)

DSIO

Relay Module (Low Voltage)

HPS

High-Pressure Switch

LV

Low Voltage

NC

Normally Closed

NO

Normally Open

PL

Plug

PWR

Power

SNB

Snubber

TB

Terminal Block

TRAN

Transformer

U

Unloader

Fig. 11A — 24-V Safety Circuit Wiring (040-070)