MOUNTING & WIRING
All wiring must comply with National Electrical Codes, local and ordinances.

Remove the cover of the thermostat and set it aside. Exercise care not to mar the mating surface
or damage the temperature sensing/operating components. CAUTION: Marring of the mating sur-
faces of the cover and enclosure could destroy the integrity of the seal causing an unsafe condi-
tion during operation of the thermostat.

Mount the thermostat base on the surface selected. See Fig. 1 for dimensions.

The base is tapped for 3/4” conduit; a 1/2” conduit adapter and a 3/4” plug are provided. Two
openings are provided. Unused openings must be properly plugged, with plug provided, prior to
applying power to the unit.

Connect the conduit to the mounted base and place the required wire into the base.

Connections are to be made to the switch terminals on the cover, Fig. 2. The cover can then be in-
stalled to the base and securely fastened utilizing the four (4) mounting screws. Immediately prior
to assembly, inspect the mating surfaces of the cover and enclosure. Do not connect if surface
are uneven or gaps exist between the cover an enclosure. Install the four (4) screws to enclosure
cover and tighten to 40-50 inch pounds.

The installer must seal each conduit run within 18” of the thermostat enclosure. This seal must be
a suitable listed hazardous location

fitting.

1.

2.

3.

4.

5.

6.

We Ship the heat in a week!

8047

183-xtTMTMd8-d

rev 1

FIGURE 1

FIGURE 2