INSTALLATION

Continued

INSTALLATION

Checking Gas Connections

WARNING: Test all gas piping and connections

for leaks after installing or servicing. Correct all leaks
at once.

WARNING: Never use an open flame to check for

a leak. Apply a noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak. Correct all
leaks at once.

CAUTION: For propane/LP gas, make sure exter-

nal regulator has been installed between propane/LP
supply and heater. See guidelines under

Connecting

to Gas Supply, page 11.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance main gas valve (con-
trol valve) and equipment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2 psig will damage heater
regulator.

2.

Cap off open end of gas pipe where equipment shutoff valve
was connected.

3.

Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas or opening main gas valve
located on or near gas meter for natural gas, or using com-
pressed air.

4.

Check all joints of gas supply piping system. Apply a noncorrosive
leak detection fluid to all joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment shutoff valve to gas supply.
Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Figure 16).

2.

Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas or opening main gas valve
located on or near gas meter for natural gas, or using com-
pressed air.

3.

Check all joints from gas meter for natural gas (see Figure 17)
or propane/LP supply tank for propane/LP gas, to equipment
shutoff valve (see Figure 18). Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles forming show a leak.

4.

Correct all leaks at once.

CHECKING GAS CONNECTIONS

Figure 18 - Checking Gas Joints for Propane/LP Gas

Figure 16 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Propane/LP
Supply
Tank

Thermostat
Gas Valve

ON

POSIT

O

PO

Open

Closed

Equipment
Shutoff
Valve

Figure 17 - Checking Gas Joints for Natural Gas

Equipment
Shutoff
Valve

Gas
Meter

Thermostat
Gas Valve

Pressure Testing Heater Gas Connections

1.

Open equipment shutoff valve (see Figure 16).

2.

For natural gas open main gas valve located on or near gas
meter. For propane/LP gas open propane/LP supply tank valve.

3.

Make sure control knob of heater is in the OFF position.

4.

Check all joints from equipment shutoff valve to thermostat
gas valve (see Figure 17 or 18). Apply a noncorrosive leak
detection fluid to all joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater, page 13). Check all other
internal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to Appliance, page 14).

8.

Replace front panel.