Mounting plate to outlet detail – Amico Ceiling Column Rigid LITE (Stationary) User Manual
Page 9
Advertising
Approval Signature
Date
Phone No.
NOTE:
1.
Gases will be manifolded for single point connections from source.
2.
All pipes will extend 8” from the top of mounting plate.
3.
Pipe stubs diameters are:
- 3/4” dia. for vacuum, WAGD, and AGSS (Type L)
-1/2” dia. for medical air, oxygen, and nitrous oxide (Type L)
-1/2” dia. for nitrogen (Type K)
4.
Exact locations of gas terminations on mounting plate will be determined after receiving the booklet.
Mounting Plate to Outlet Detail
8
Amico Pipeline