Step 1:
Remove all secondary check parts from the
existing outlets. Replace the NCG rubber seat with
Amico #15 O-Ring.
Retro-Fit Instructions
Step 2:
Thread the Amico Retro-Fit rough-in assembly to
the existing NCG rough-in.
Important Note
Due to unknown factors of the existing equipment, projects requiring Retro-Fit Conversions must be fully investigated by
the installer.
It is the responsibility of the installer to determine if the Retro-Fit will function correctly and if additional components are
required. Amico is not responsible for any additional components required.
O-VC-OH1-TOOL
Amico Tool
Hole for Screw Driver
(to loosen & tighten)
Existing NCG
Rough-In
O-Ring
(H-ORING-015VTN)
NCG Original Rubber
Seat (to be removed &
replaced by #15 O-Ring)
Existing NCG
Rough-In
Back Rough-In
Assembly Kit
(O-VC-NCG-U-GAS)