Step 1:

Remove all secondary check parts from the

existing outlets. Replace the NCG rubber seat with

Amico #15 O-Ring.

Retro-Fit Instructions

Step 2:

Thread the Amico Retro-Fit rough-in assembly to

the existing NCG rough-in.

Important Note

Due to unknown factors of the existing equipment, projects requiring Retro-Fit Conversions must be fully investigated by

the installer.

It is the responsibility of the installer to determine if the Retro-Fit will function correctly and if additional components are

required. Amico is not responsible for any additional components required.

O-VC-OH1-TOOL

Amico Tool

Hole for Screw Driver

(to loosen & tighten)

Existing NCG

Rough-In

O-Ring

(H-ORING-015VTN)

NCG Original Rubber

Seat (to be removed &

replaced by #15 O-Ring)

Existing NCG
Rough-In

Back Rough-In

Assembly Kit

(O-VC-NCG-U-GAS)