Baseline Systems BACnet Manager User Manual

Page 3

Advertising
background image

Software Setup—BACnet Manager

1. Run the BACnet Manager application by clicking on the desktop

shortcut to the menu item under the BaseManager folder in
Programs—Unblock Firewall if prompted.

2. Review the Status tab on the BacManager window and verify

that the BaseStation 3200 controllers have been processed.

BACnet Objects

1. The BACnet Network Number = 444

2. Connection = BACnet/IP

3. BaseStation 3200 Controller Object Model:

a. Accumulator Object—one for each flow device. This

reports the accumulated water used for the flow device.
This is updated daily.

b. Analog Input—one for each flow device. This reports the

water used for the previous day. This is updated daily.

c. Binary Input—there are nine of these and they each

represent an alert state for the controller:
- Upper Flow Shutdown
- Two-wire High Current Shutdown
- High Temperature Shutdown (not used)
- Watering Paused
- Failure to Connect
- Dial Set To OFF
- Valve Failure
- Device Failure (unable to communicate)
- Program Overrun

d. Device—this represents the 3200 controller