Troubleshooting for Initial Installation

Problem

Cause

Solution

Er1 is displayed

The S100 cannot communicate with
the biSensor

• Check the wiring and connections
to the biSensor
• Make sure the correct valve wire
and common wire are used
• After making repairs follow the
“Verify biSensor Communication”
instructions under Step 1 at the end
of this section

Er2 is displayed

The S100 has detected excessive
current while trying to communicate
with the biSensor

• Double-check the wiring and
connections to the biSensor
• Make sure the common and
biSensor wires are correctly
connected
• Check for a faulty valve solenoid
• After making repairs follow the
“Verify biSensor Communication”
instructions under Step 1 at the end
of this section

Er3 is displayed
along with
another error

There was a problem during the S100
24-hour moisture threshold
calibration

• This error is accompanied by one
of the other error codes
• Refer to the other Er# for possible
solutions

Er4 is displayed

(this is a warning
message,
pressing”Sensor
Update”will
clear this)

Unexpected reading during 24-hour
moisture threshold calibration, final
reading was not substantially
different from first

(please refer to

the Er4 code on page 17)

• Follow the instructions under Step
5 at the end of this section
• Make sure no extra water is
applied to the biSensor after
calibration starts or the S100 may
set a non-optimal threshold

Er5 is displayed

An interruption of the 24-hour
moisture threshold calibration
occurred due to attempted valve
activation

• Check the valve the biSensor is
connected to for proper operation
• After making repairs follow the
instructions under Step 5 at the end
of this section (turn off controller
during 24-hour moisture threshold
calibration)

Er6 is displayed

Unexpectedly low reading during 24-
hour moisture threshold calibration

• Follow the instructions under Step
5 at the end of this section

Display is blank.
LED’s are off

S100 is not receiving 24 VAC

• Make sure the 24VAC transformer

is plugged in
• Check that the two 24VAC lines
and the common from the S100 are
wired correctly

Display flashes
random
segments or 88.8

The S100 common is not connected
correctly

• Make sure the common from the
S100 is connected to the valve
common of the sprinkler controller