Pump & pipe installation instructions – Basement Watchdog Emergency User Manual

Page 7

Advertising
background image

Page 6

Pump & Pipe
Installation Instructions

INSTALLATION C:
DIRECT DISCHARGE TO THE OUTSIDE OF THE
BUILDING FOR NARROW SUMP PITS
(Diagram C)

Unplug the main AC pump when installing
the backup pump to avoid electric shock.
Failure to do so could cause serious injury or
death.

1. Attach an “L” bracket to the discharge pipe of

the main AC pump with two (2) stainless steel
hose clamps. Position the bracket so the
bottom of the “L” is just above the top of the
main pump, and out of the way of any float
switch on the main pump.

2. (a) Remove the black bottom strainer of the

pump by pressing in the two tabs on the
strainer and pushing down. There are holes
suitable for mounting on the bottom of the
strainer. (b) Using the #8-32 x ¾” stainless
screw, washer and nut, attach the strainer to
the “L” bracket. (c) Once the strainer is

attached, simply press the rest of the pump
onto the mounted strainer.

3. Secure the pump wire so that the plug on the

end will not fall into the sump. Attach the
wire to the pipe with a piece of tape.

4. Cut a piece of 1½” rigid PVC pipe long enough

to reach from the elbow of the backup pump
to one (1) foot above the floor. Prime and
cement it to the 1½” pipe adapter, then screw
the adapter into the pump.

5. Attach a union or check valve to the top of

the 1½” PVC pipe. This will allow the pump
to be removed easily, should the need arise.

The path of the rest of the pipe and the details
of each installation will vary. Using sound
plumbing practices, route the discharge pipe to
an exterior wall via the shortest path with the
fewest turns. More turns will reduce the
pumping capacity. The pipe section exiting the
building should be on a downward slope so that
the water in the pipe will exit outside instead of
returning to the sump pit. Be sure to seal the
hole in the wall where the pipe exits, and prime
and cement or clamp all connections securely to
prevent leaking. When directly discharging to

the outside of the building, no check valve is
required. However, a check valve will prevent
water from flowing back into the pit when the
pump has stopped.

If you use more than a total of 20 feet of pipe
(including vertical and horizontal runs) in the
installation, install a check valve in place of
the union. Make sure it is installed with the

arrow pointing up or it will not prevent the
backflow of water. When a check valve is used,
a 1/8” hole must be drilled in the PVC pipe
above the Basement Watchdog pump. Drill the
hole at a 45° angle toward the bottom of the
sump to avoid splashing water outside the
sump pit. Make sure the hole is above the
water line, and below the check valve. If a hole
is not drilled above the pump, an air lock may
prevent the pump from operating.

PUMP WIRE

CHECK
VALVE

HOSE
CLAMPS

"L" BRACKET

FLOOR

JOIST

MAIN
AC PUMP

RIGID

1-1/2"

PVC PIPE

UNION

OR CHECK

VALVE

PIPE ADAPTER

DRILL 1/8" HOLE

IF CHECK

VALVE USED

BASEMENT

WATCHDOG

PUMP

DRAIN TILE

SLOPE

PIPES
DOWN

Diagram C

2c

4

3

CAUTION

!

DANGER

1

2b

2a

“L” BRACKET

5

Advertising