Chatsworth Products Electronic Lock Upgrade Kit 16147-062 User Manual

Electronic locking system for cpi cabinets, Electronic locking system

Advertising
background image

P R O D U C T A P P L I C AT I O N

Keypad Module (recommended) — Enter an

authorized access code on the Keypad Module to
open a handle. The Keypad Module can be placed

on or near the cabinets and can open any of the

cabinet handles in the system.

Communications Module (required) — Provides a single IP

addressable network connection for the Electronic Locking

System and is used to setup and configure the system.

Each Communications Module can support any

combination of up to 64 Electronic Lock Control

Modules (512 handles, 256 cabinets), 64 Keypad

Modules and 64 Proximity Card Reader Modules. Control

access to equipment with computer terminals using the

included lock control software. Provide alarm outputs for

unauthorized entries. The software also keeps a log of

each access attempt and all configuration changes.

Electronic Lock Upgrade Kit (required)

— Replace the mechanical lock on the

cabinet’s swing handle with an electronic

solenoid that releases the spring-loaded
handle when the correct code is entered.

When the correct code is entered, the

handle springs open allowing the door to

be opened.

800-834-4969

[email protected]

www.chatsworth.com

Electronic Locking System

Electronic Lock Upgrade Kit (2 per cabinet)
with Electronic Lock Extension Cable

Electronic Lock Control Module (8 handle)

Proximity Card Reader Module

Keypad Module
with Keypad Module Cable

Communications Module

Electronic Lock Control Module (required) —

Connects upgraded electronic locks to the

Electronic Locking System and controls the

solenoid that opens the cabinet handles.

Each Electronic Lock Control Module
connects eight handles (four cabinets) to

the system. Each handle can have up to

five access codes and can be assigned to

24 user groups. The Electronic Lock Control

Module also reports the status of the handle

(opened or closed).

Proximity Card Reader Module (optional) — Use with the

Keypad Module. The proximity card acts like a key replacing the

access code. The proximity card can be programmed with a

specific handle access code or with up to 24 user group codes to

open multiple cabinets. Proximity cards can also be programmed

to open handles a specific number of times and to expire at a

specific time and date.

Electronic Locking System For CPI Cabinets

Automate access control and monitoring in your data center, computer
room and network facilities with the Electronic Locking System.

• Automate data center cabinet access control and monitoring
• IP addressable system increases security
• Assign and program individual user ID access codes
• Access cabinets via a network-connected computer, keypad or

proximity cards

• Create a log entry for each access attempt and configuration change
• Monitor handle conditions — opened or closed
• Forward SNMP traps to designated computers during alarm conditions
• Quickly update the system configuration and users privileges
• Easily add modules as your network grows

Rear

View

Advertising