EG-Baumusterprüfbescheinigung

EC type test certificate

Attestation d'examen CE de type

PTB 03 ATEX 2146

Kennzeichnung

Marking

Marquage

II 1G Ex ia IIc T6 Ga

Strom Li

Current Li

Courant Li

< 37 mA

Spannung Ui

Voltage Ui

Tension Ui

< 13,5 VDC

Leistung Pi

Power Pi

Puissance Pi

< 0,125 W

Innere Kapazität Ci

Internal capacitance Ci

Capacité interne Ci

< 50 nF

Innere Induktivität Li

Internal inductance Li

Inductance interne Li

< 0,2 mH

Arbeitstemperatur Ta (Temp. Klasse T5)

Operating temperature Ta (Temp. T5)

Température de fonctionnement Ta (Temp. T5)

-20...+60°C

Arbeitstemperatur Ta (Temp. Klasse T6)

Operating temperature Ta (Temp. T6)

Température de fonctionnement Ta (Temp. T6)

-20...+40°C

Sicherheitstechnische Daten
Safety-related data
Données de sécurité

Installation und Inbetriebnahme der Geräte dürfen nur durch Fachpersonal
durchgeführt werden. Das Fachpersonal muss mit den Vorschriften für
explosionsgefährdete Umgebung vertraut sein.

Einbauhinweise (genereller Einsatz)
- Wartungsintervalle gemäss Schutzzone sind einzuhalten. Alle Komponenten,
von denen die Zündschutzart abhängt, sind auf Unversehrtheit zu prüfen
- Gerät und Anschlusskabel müssen vor UV-Licht geschützt montiert werden
- Das Metallgehäuse muss mit dem Potentialausgleichsystem der Anlage
leitend verbunden sein

Zusätzliche Einbauhinweise für den Einsatz in Kategorie 1
- Die Anschlussleitung und der Sensor sind innerhalb der Kategorie 1 fest zu
verlegen
- Die Anchlussleitung muss so verlegt werden, dass diese in der Kategorie 1
gegenüber elektrostatischer Aufladung geschützt ist
- Die Anschlussleitung ist nach EN 60079-26 in den Bereich Kategorie 1
hineinzubringen (IP67)

Wartung / Prüfung
- Im Fehler- oder Störfall des Gerätes soll der Hersteller kontaktiert werden
- Defekte Geräte müssen ersetzt werden, keine Reparatur möglich
- Es dürfen keine Modifikationen am Gerät vorgenommen werden

Installation und Inbetriebnahme

Installation and commissioning

Installation et mise en service

Installation and commissioning may only be performed by qualified personnel. The
qualified personnel must be familiar with the regulations for potentially explosive
environments

Installation notes (general use)
- Maintenance intervals in accordance with the protection zone must be observed.
All components which the type of protection depends on must be checked for
sound condition.
- Device and connection cable must be installed so that they are protected from
UV light
- The metal housing has to be conductively connected to the potential equalization
system

Additional installation notes for use in category 1:
- Within category hazardous areas sensor and cable must be securely mounted
- The connection cable must be installed so that it is protected from electrostatic
charge in category 1
- Sensor cables leading into category 1 hazardous areas must be installed
according to the guidelines as specified in EN 60079-26 (IP 67)

Maintenance/inspection
- The manufacturer should be contacted in case of device error or malfunction
- Defective devices must be replaced, repair is not possible
- Modification of the device is not permitted

Seul un personnel spécialisé est autorisé à procéder à l'installation et à la mise en
service des appareils. Le personnel spécialisé doit parfaitement connaître les directives
relatives aux environnements à risque d'explosion

Consignes de montage (usage général)
- Respecter les intervalles d'entretien suivant la zone de protection. Vérifier l'intégrité
de tous les composants dont dépend le type de protection incendie
- Procéder au montage de l'appareil et du câble de raccordement à l'abri des rayons UV
- Le boîtier métallique doit être connecté de manière conductrice le système
équipotentielle

Consignes de montage supplémentaire pour une utilisation dans la catégorie 1:
- En zone de catégorie 1 détecteurs et câbles doivent êtres montés de manière sécurisée
- Le câble de raccordement doit être installé de façon à être protégé de la charge
électrostatique dans la catégorie 1
- Les câbles et connecteurs entrant en zone de catégorie 1 doivent être installées
confornément aux directives spécifiées par la norme EN 60079-26 (IP 67)

Entretien / Contrôle
- En cas de dysfonctionnement ou de panne de l'appareil, contacter le fabricant
- Les appareils défectueux doivent être remplacés, aucune réparation possible
- Ne procéder à aucune modification sur l'appareil