Carrier 38AK012 User Manual

Page 7

Advertising
background image

Table 5 — Electrical Data

UNIT

38

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

MIN

MAX

RLA

LRA

FLA

MCA

MOCP

AK007

208/230-3-60

187

254

21.8

142

1.9

25.6

35

460-3-60

414

508

9.6

72

1.0

12.9

15

575-3-60

518

632

7.6

58

1.9

11.4

15

220-3-50

198

242

19.0

142

1.0

25.6

35

400-3-50

360

440

9.5

72

1.0

12.9

15

AK008

208/230-3-60

187

254

28.8

195

3.8

39.8

45

460-3-60

414

508

14.7

95

1.9

20.3

20

575-3-60

518

632

10.8

80

1.9

15.4

15

220-3-50

198

242

28.8

195

1.5

37.5

45

400-3-50

360

440

14.7

90

1.5

19.9

20

AK012

208/230-3-60

187

254

37.8

239

3.1

46.2

60

460-3-60

414

508

17.2

125

1.4

22.7

30

575-3-60

518

632

12.3

80

1.4

19.3

25

220-3-50

198

242

37.8

239

1.4

46.2

60

400-3-50

360

440

17.2

125

1.4

22.7

30

AKS008

208/230-3-60

187

254

31.5

160

3.1

42.5

50

380-3-60

342

418

19.0

75

2.2

26.0

35

460-3-60

414

508

15.7

80

1.4

21.0

25

575-3-60

518

632

12.6

64

1.4

17.2

20

220-3-50

198

253

31.5

160

1.4

42.5

50

400-3-50

342

460

15.7

80

1.4

21.0

25

AKS009

208/230-3-60

187

254

39.7

198

3.1

52.7

70

380-3-60

342

418

24.0

93

2.2

32.2

40

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

220-3-50

198

253

39.7

198

1.4

52.7

70

400-3-50

342

460

19.9

99

1.4

26.3

35

AKS012

208/230-3-60

187

254

39.7

198

3.1

52.7

70

380-3-60

342

418

24.0

93

2.2

32.2

40

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

220-3-50

198

253

39.7

198

1.4

52.7

70

400-3-50

342

460

19.9

99

1.4

26.3

35

LEGEND

CSA

Canadian Standards Association

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code (U.S.A. Standard)

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB =452 v
BC =464 v
AC =455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

(AB) 457 - 452 =5 v
(BC) 464 - 457 =7 v
(AC) 457 - 455 =2 v
Maximum deviation is 7 v.

Determine percent voltage imbalance

7

% Voltage Imbalance =100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

3. The 575-v units are CSA only.
4. The 380 v, 60 Hz units and all 50 Hz units are

not UL or CSA listed.

7