Manual_GK473_Profibus_EN.doc 14/16

Baumer IVO GmbH & Co. KG

04.05.11

Villingen-Schwenningen,

Germany

• The gateway itself will indicate error if the error is due to a gateway command (code „@“).

Furthermore, the gateway will also indicate error if the error status results from any automatic
function (for example cyclic SPA scanning).


The gateway error messages comprise dummy address 20h, command „@“ (40h), sub-command „e“
(65h) as well as the error number. The message is of the following format:

Zhl Adr Cmd Scmd „S“

data

message

zz

20h 40h 65h

53h

30h

30h

30h

30h

30h

30h

30h 30h 00h 00h

00h


To maintain the figure description usual in RS485 communication, all error numbers provide an offset
of 20h.

error number-

error occurred

20h no

error

21h

void sign in protocol

22h

SPA indicates repeatedly CRC error

23h

data value beyond the permitted range

24h

number of commands/data beyond the permitted
range

25h

timeout during waiting for SPA response, with
transparent commands only

26h

unknown gateway command (@xxx)

27h...2Fh reserved


5.7. Error and warning signals (diagnostic data)

Diagnostic data are only for transmission of messages indicating any gateway error status that might
endanger Profibus operation.

Messages relating to SPA communication are processed by the standard data exchange (see error
messages data exchange). Only exception is indication of a lost SPA (error 20h) which does not react
anymore even after having tried three times.

Diagnostic data are of 11 byte in length. The first 6 byte are used for standard diagnostic data for
automatic evaluation by PLC, the remaining 5 byte for external gateway diagnosis. The last byte
contains the gateway error information.

diagnostic byte

type

1

standard

standard diagnostic byte 1

2

standard

standard diagnostic byte 2

3

standard

standard diagnostic byte 3

4

standard

Master address after parameterizing (previously FFh)

5

standard

Ident-number high byte

6

standard

Ident-number low byte

7

external

information on length of external diagnosis (05h)

8

external

reserved, always 00h

9

external

reserved, always 00h

10

external

reserved, always 00h

11

external

error number, -see chart below


error number

errors occured

00h no

error

01h

selftest: program memory error (flash)

02h

selftest: ERM error

03h

selftest: ROM error (EEprom)

21h

loss of SPA connected

80h..8Fh internal

error