Baumer BA UNxK09 IO User Manual

Page 12

Advertising
background image

en_BA_UNXK 09-IO-Link.doc

12/18

Baumer Electric AG

24.04.2012/haa

Frauenfeld, Switzerland

3) Two window thresholds shall be set at 40mm (A) and at 60mm (B) -> (characteristic 3).

Setting the window function:
Switching- / Teach function: 1

Point A absolute in tenth of mm:

400

 0190 hex (= Switching point A)

Point B absolute in tenth of mm:

600

 0258 hex (= Switching point B)

Parameter to be written:
Switching points work:

01900258 hex

5.2.3.2 Example Teach-in on object

The switching points are taught against an object.

Figure 5: Teaching the switching points

In order to obtain an inverted switching (characteristic 4) the distance from the sensor to Switching point A
must be bigger than the one to Switching point B.

Assigning of parameter
Switching-/Teach function
to a switching point or a
window threshold

Position the object at the

switching point.

Switching point

Window threshold

Position the object at the
switch-on point.

Teach switching point in interim

register using command

Teach-in switching point A.

Position the object at the switch-
off point.

Teach switching point in interim

register using command

Teach-in switching point A or

Teach-in switching point B.

Interim register switching

points interim enables

reading and verification of

taught values at all times.

Teach switching point in interim

register using command

Teach-in switching point B.

Transfer switching points from

interim register to work register

using command Transfer

switching points and switch

to active.

Transfer switching points from
interim register to work register
using command Transfer
switching poin
ts and switch to
active.

After value export to work
register, the interim register will
be restored to FFFF FFFF hex.